Simpool pH model
Programmable digital peristaltic pump
4.3 OFF STATUS ALARM
If the switch is left on the OFF position, after 20 minutes the switch alarm is activated and signalled by the pump in
the following way:
Audio signal via the buzzer (if there is one on the pump) and if enabled (see b.En on the "Settings Menu")
with a frequency of 1 second on and 1 second off;
flashing red LED;
"OFF" flashing on the display;
Just set the switch to ON to disable it.
4.4 OFA ALARM
The OFA alarm is a dosing alarm that is activated when there is no specific variation of the pH value read when the
corrector is dosed during a set time frame (OFA time).
The observation time, OFA, can be set from 300 to 999 seconds or it can be disabled (OFF) from the Settings
Menu and it is enabled when the pump starts dosing (Ton of the pH cycle period): the alarm is activated if the pH
value read does not vary during the OFA time at least for the value set in A.PH (from 0.05 to 0.99 pH).
The OFA alarm is reported by the pump in the following way:
Audio signal via the buzzer (if there is one on the pump) and if enabled (see b.En on the "Settings Menu")
with a frequency of 1 second on and 1 second off;
flashing red LED;
"OFA" flashing on the display;
Dosage stop (the pump is stopped);
The alarm will be disabled if:
The pH value is reported in the window featuring the Setpoint ± r.PH values, where r.PH ranges from 0.05 to
0.99 pH (Settings Menu);
Use the switch or the power supply to turn it on or off;
4.5 POOL ALARM
If the pH value read is below pH 5.00 or above pH 9.00, the pump reports a Pool Alarm.
The Pool Alarm is reported in the following way:
Audio signal via the buzzer (if there is one on the pump) and if enabled (see b.En on the "Settings Menu")
with a frequency of 1 second on and 1 second off;
flashing red LED;
"PEr" flashing on the display;
Dosage stop (the pump is stopped);
You can automatically exit the alarm status of the pH value returns above pH 5.00 or below pH 9.00.
4.6 RANGE ALARM
If the pH value read is below pH 6.00 or above pH 8.00, the pump reports a Range Alarm.
The Range Alarm is reported in the following way:
Audio signal via the buzzer (if there is one on the pump) and if enabled (see b.En on the "Settings Menu")
with a frequency of 1 second on and 1 second off;
flashing red LED;
"rEr" flashing on the display;
When the Range alarm is reported, the pump keeps on operating as normal.
You can automatically exit the alarm status of the pH value returns above pH 6.00 or below pH 8.00.
Figure 20 briefly illustrates the pump activation in the Pool and Range Alarms in relation to the pH.
ADSP7000407
Fig. 20 - Range Alarm and Pool Alarm
rev. 1.2
INSTRUCTION AND MAINTENANCE MANUAL
27/03/2015
ENGLISH
60/313