Micropilot FMR20 MODBUS RS485
Adresse
Nom
5420
LCRS_
FREEFIELDMOD
E
5421
LCRS_
HIGHBLOCKDIST
ANCE
5423
LCRS_ MAP_
ENDX
5425
LE_ PVUNIT
5426
MODB_
RUNMODE
5427
MODB_
MEASUREMENT
_ TRIGGER
5284
FMR_ LIN_
TABLE
5348
FMR_ LIN_
TABLE_ 2
Adresse Nom
5428
MODB_ PROTOCOL
5429
MODB_ PARITY_ AND_
DATABITS
5430
MODB_ STOPBIT
5431
MODB_ BAUDRATE
5432
MODB_ ADDRESS
Endress+Hauser
Nombre de
Accès
registres
• Service
• Opérateur
1
• read/write
• read only
2
• read/write
• read only
2
• read/write
• read only
1
• read/write
• read only
1
• read/write
• read only
1
• read/write
• read/write
64
• read/write
• read only
64
• read/write
• read only
15.1.8

Section : Communication

Registre Accès
Gamme
• Service
• Opérateur
1
• read/write
RTU: 974
• read only
ASCII: 973
1
• read/write
8N: 3498
• read only
8O: 3499
8E: 3500
7O: 3501
7E: 3502
1
• read/write
1 Stop Bit: 3503
• read only
2 Stop Bit: 3504
1
• read/write
1200: 975
• read only
2400: 976
4800: 977
9600: 978
19200: 979
1
• read/write
1 ... 200
• read only
Gamme
Type de
données
off: 33004
enum16
on: 33006
0 ... 20
float32
0 ... 21,8
float32
voir paramètre
enum16
Unité après
linéarisation
stopped: 3493
enum8
continuous: 1380
single-shot: 3494
idle: 33296
enum8
measure: 32965
-inf to inf
float32Point
-inf to inf
float32Point
Type de
données
enum8
enum8
enum8
enum16
uint8
Menu de configuration
Unité SI
Description
-
Switch to free
field parameters
m
Blocking
distance
(distance from
sensor which is
not evaluated)
m
End-point of
overlay map
(factory map +
custom map)
-
Level unit
-
Run-Mode
-
Measurement-
Trigger (only
used if MODB_
RUNMODE is
either stopped or
single-shot)
m → m³
Lower half of
linearization
table (X1, Y1,
X2, Y2, ...)
m → m³
Upper half of
linearization
table (X17, Y17,
X18, Y18, ...)
Unité SI Description
-
Modbus protocol
-
Modbus transmission
-
Modbus transmission
-
Modbus baud rate
-
Modbus slave address
67

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Modbus rs485

Table des Matières