PREMASREG
711x - VA
Schematic diagram
ON
DIP
1 2 3 4 5 6
Plug for
display
NC
12
Normally Closed
COM Common
11
13
NO
Normally Open
DIP-Schalter 4 und 6 sind nicht belegt!
Pin assignment
(M12)
2
3
4
11 10
1
5
12
9
6
8
7
1
+UB 24 V AC / 15...36 V DC
2
Output pressure 0 -10 V [Pa]
3
free
4
–UB GND
5
free
6
free
7
COM Common
8
NC Normally Closed
9
NO Normally Open
DIP switches for pressure range setting, output attenuation and zero compensation:
10
free
11
free
Pressure range
(selectable) – max. measuring range (default) is depending to the type of device
12
free
0...100 Pa
0...1000 Pa
0...300 Pa
0...2000 Pa
0...500 Pa
0...3000 Pa
0...1000 Pa
0...5000 Pa
Measuring range mode
(Mode selectable)
Unidirectional ( 0 ...+MR ) (default)
Bidirectional (–MR ...+MR )
PREMASREG
SET-Setting relay
Pushbutton
switchpoint
Zero point setting
SET
AUTO
ZERO
Offset correction
ca. ±10 % of final value
OFFSET
min. max.
1
+UB 24V AC / 15...36 V DC
2
Output pressure 0-10 V [Pa]
3
–UB GND
2
3
4
11 10
1
5
12
9
6
8
7
PREMASREG
1
+UB 24 V AC / 15...36 V DC
2
Output pressure 0 -10 V [Pa]
3
free
4
–UB GND
5
free
6
free
7
COM Common
8
NC Normally Closed
9
NO Normally Open
10
free
11
free
12
free
–100...+100 Pa
–300...+300 Pa
–500...+500 Pa
–1000...+1000 Pa
DIP
Measurement signal filtering
3
(Time interval selectable)
OFF
10 s (default)
O N
1 s
3-wire-
®
711x - U W
connection
®
711x - U W
DIP
1
–1000...+1000 Pa
OFF
–2000...+2000 Pa
O N
–3000...+3000 Pa
OFF
–5000...+5000 Pa
O N
13
PREMASREG
-
-
230V AC
+
+
24V AC/DC
1 2 3
DIP
2
OFF
OFF
O N
O N
DIP
5
OFF
O N
®
711x - U W
PLC
PC