Télécharger Imprimer la page

S+S Regeltechnik HYGRASGARD RPFF Série Notice D'instruction page 11

Masquer les pouces Voir aussi pour HYGRASGARD RPFF Série:

Publicité

Les langues disponibles

Les langues disponibles

G
®
HYGRASGARD
The calibratable pendulum room humidity and temperature sensor HYGRASGARD
RPFF - 25 ⁄ RPFTF - 25 with pluggable metal sinter filter, housing made of impact-resistant plastic, with ⁄ without optional display. It measures the
relative humidity and ⁄ or the temperature of the air and converts the measurands into a standard signal of 0 - 10 V or 4...20 mA.
It has four switchable temperature ranges. The sensor is applied in non-aggressive dust-free atmospheres in refrigeration, air conditioning, ventilation
and clean room technology, hotels, technical rooms, meeting rooms and convention centres. These measuring transducers are designed for exact
detection of temperature and humidity. A digital long-term stable sensor is used as a measuring element for humidity and temperature measurement.
The sensor is appropriate for ceiling and duct installation, or for integrating it into equipment. The sensor is factory-calibrated; an environmental
precision adjustment by an expert is possible.
TECHNICAL DATA
Power supply:
Working resistance:
Load resistance:
Power consumption:
Sensors:
Sensor protection:
HUMIDIT Y
Measuring range, humidity:
Operating range, humidity:
Deviation, humidity:
Output, humidity:
TEMPERATURE
Measuring range, temperature:
Operating range, temperature:
Deviation, temperature:
Output, temperature:
Ambient temperature:
Long-term stability:
Housing:
Housing dimensions:
Cable connection:
Electrical connection:
Connection cable:
Protective tube:
Protection class:
Protection type:
Standards:
Optional:
RPFF ⁄ RPFTF (± 2,0 %), RPFF - 25 ⁄ RPFTF -25 (± 1,8 %)
24 V AC (± 20 %); 15...36 V DC for U variant
15...36 V DC for I variant, depending on working resistance, residual ripple stabilised ± 0.3 V
R
(ohm) = (U
-14 V) ⁄ 0.02 A for I variant
a
b
R
> 5 kOhm for U variant
L
< 1.1 VA ⁄ 24 V DC ; < 2.2 VA ⁄ 24 V AC
digital humidity sensor with integrated temperature sensor,
low hysteresis, high long-term stability
RPFF ⁄ RPFTF:
RPFF - 25 ⁄ RPFTF - 25: pluggable measuring head (probe) with metal sinter filter,
0...100 % r. H. (output corresponding to 0 -10 V or 4...20 mA)
0...95 % r. H. (without formation of dew)
RPFF ⁄ RPFTF:
RPFF - 25 ⁄ RPFTF - 25: typically ± 1.8 % (10...90 % r. H.) at +25 °C, otherwise ± 2.0 %
0 - 10 V for U variant
4...20 mA for I variant, see load resistance diagram
multi-range switching with 4 switchable measuring ranges (see table)
–35...+35 °C; –35...+75 °C; 0...+50 °C; 0...+80 °C
(output corresponding to 0 -10 V or 4...20 mA)
–35...+80 °C
typically ± 0.2 K at +25 °C
0 -10 V or 4...20 mA or Ohm value
RPFF ⁄ RPFTF:
RPFF - 25 ⁄ RPFTF - 25: storage –35...+85 °C;
± 1 % per year
plastic, UV-resistant, material polyamide, 30 % glass-globe reinforced, 
with quick-locking screws (slotted ⁄ Phillips head combination),
colour traffic white (similar to RAL
RPFF ⁄ RPFTF:
RPFF - 25 ⁄ RPFTF - 25: 126 x 90 x 50 mm (Tyr 2)
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (on request)
2-, 3-, or 4-wire connection (see connecting diagram), 0.14 - 1.5 mm² via terminal screws
RPFF ⁄ RPFTF:
RPFF - 25 ⁄ RPFTF - 25: KL = 2 m
stainless steel V2A (1.4301),
RPFF ⁄ RPFTF:
RPFF - 25 ⁄ RPFTF - 25: Ø = 18 mm (16 mm), L = 120 mm
III (according to EN 60 730)
RPFF ⁄ RPFTF:
RPFF - 25 ⁄ RPFTF - 25: IP 65 (according to EN 60 529)
CE conformity, according to EMC directive 2014 ⁄ 30 ⁄ EU,
according to EN 61326-1, according to EN 61326-2-3
display with iillumination, for displaying ACTUAL temperature and ⁄ or ACTUAL humidity
RPFF ⁄ RPFTF:
RPFF - 25 ⁄ RPFTF - 25: three-line, cutout approx. 70 x 40 mm (W x H), (Tyr 2)
®
RPFF ⁄ RPFTF with plastic sinter filter or HYGRASGARD
plastic sinter filter, Ø 16 mm, L = 35 mm, exchangeable
(optional metal sinter filter, Ø 16 mm, L = 32 mm)
Ø 16 mm, L = 88.5 mm, exchangeable
typically ± 2.0 % (20...80 % r. H.) at +25 °C, otherwise ± 3.0 %
storage –5...+60 °C;
operation –5...+60 °C
operation –30...+70 °C
9016),,
housing cover for display is transparent!
72 x 64 x 37,8 mm (Tyr 1 without display)
72 x 64 x 43,3 mm (Tyr 1 with display)
2
PVC, LiY Y, 6 x 0.14 mm
, K L = approx. 2 m (other lengths optional)
Ø =16 mm, L = 142 mm
IP 67 (according to EN 60 529) Housing tested, TÜV SÜD, Report No.713139052 (Tyr 1)
IP 65 (according to EN 60 529) Pendulum with sleeve
two-line, cutout approx. 36 x15 mm (W x H), (Tyr 1)
11
2,0% = Rev. 2021 - V17
1,8% = Rev. 2021 - V27
®

Publicité

loading

Ce manuel est également adapté pour:

Hygrasgard rpftf série