Télécharger Imprimer la page

PLYMOVENT SMARTONE Manuel Opérateur page 5

Publicité

Les langues disponibles

Les langues disponibles

Safety information:
1. When replacing the filter cartridge always switch off the power to the control box.
(see separate instruction: Replacing the filter cartridge)
2. When emptying the dust bin always switch off the power to the control box.
(see separate instruction: Emptying the dust bin)
3. When replacing the filter cartridge or emptying the dust bin always use
protective gloves and mask.
4. Be careful when replacing the filter cartridge, as it's weight can be substantial,
depending on the type of collected particles.
5. The control box should only be opened by a qualified electrician.
6. Ear protections should always be used when the cleaning system is serviced as the
sound level is high when the diaphragm valves are activated.
7. Filter cartridge hatches must never be opened during operation.
user information,control box
the control box contains a controller card for sequential
pulsing in the Ram-Air™ cleaning system.
the electrical coil on the compressed air valve is activated
from the controller card. a built-in monitoring system checks
continuosly the filter condition of the filter cartridge.
cleaning is performed automatically when the pressure
loss over the filter cartridge reaches the pre-set level.
the cleaning goes on until the pre-set time runs out.
the clean card will again check if the pressure switch
is still engaged or not, if so the next cleaning cycle will start
and so on.
When the cleaning does not stop after repeted cleaning
cycles the filter cartridge must be changed.
the cleaning can also be started manually by pressing the
yellow switch (d). the cleaning goes on until the pre-set time
runs out.
an alarm monitors the electrical circuits in the Smart"one" .
if an error occurs the led (h)is lighted.
1. control box,Starting up the filter
a. Start up the filter/fan by turning the mainswitch in position 1.
When the main switch is turned on the indicator (a) is on.
b. the fan can be started or stopped by pressing the button(b).
While the fan is running the indicator(c) is on.
c. the filters self cleaning system is activated automatically by a pressure gover-
nor. in this case the cleaning system automatically starts when the
pressure rises above normal.During cleaning operation the indicator(i)
is on.the cleaning system will stop when the pressure returns to normal.
the number of cleaning cycles is determined by the adjusted values on the
potentiometers.(f.g)
the filter claening can also be started by pressing button (d). in this case the
system will be activated manually.
(e)-pulse time
(f)-pause time
(g)-cycle time
(h) warning led.
071113/0 SmartOne
a
c
h
P
T
e
f
g
i
d
b
EN - 4

Publicité

loading