To Connect The Shut-Off Valve; To Connect The Electricity Meters - Daikin EABH16DF6V Manuel D'installation

Masquer les pouces Voir aussi pour EABH16DF6V:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 56
4 Installation
Model (power
Connections to backup heater power
supply)
*6V (6V: 1N~ 230 V)
SWB
F1B
1N~, 50 Hz
230 V AC
*6V (6T1: 3~ 230 V)
K5M
SWB
F1B
Q1DI
3~, 50 Hz
230 V AC
*9W (3N~ 400 V)
SWB
F1B
Q1DI
3N~, 50 Hz
400 V AC
F1B  Overcurrent fuse (field supply). Recommended fuse:
4‑pole; 20 A; curve 400 V; tripping class C.
K5M Safety contactor (in the switch box)
Q1DI Earth leakage circuit breaker (field supply)
SWB Switch box
X6M Terminal (field supply)
Installation manual
12
supply
2
4
6
14
K5M
1
3
5
13
X6M
1
3
5
7
I
I
I
I
2
4
6
8
Q1DI
L
N
2
4
6
14
1
3
5
13
X6M
1
3
5
7
I
I
I
I
2
4
6
8
L1 L2 L3
2
4
6
14
K5M
1
3
5
13
X6M
1
3
5
7
I
I
I
I
2
4
6
8
L1 L2 L3
N
NOTICE
Do NOT cut or remove the backup heater power supply
cable.
4.4.5

To connect the shut-off valve

INFORMATION
Shut-off valve usage example. In case of one LWT zone,
and a combination of underfloor heating and heat pump
convectors, install a shut-off valve before the underfloor
heating to prevent condensation on the floor during cooling
operation. For more information, see the installer reference
guide.
1 Connect the valve control cable to the appropriate terminals as
shown in the illustration below.
NOTICE
Wiring is different for a NC (normally closed) valve and a
NO (normally open) valve.
NO
21 28
X2M
X1M
M2S
2 Fix the cable with cable ties to the cable tie mountings.
4.4.6

To connect the electricity meters

INFORMATION
In case of an electricity meter with transistor output, check
the polarity. The positive polarity MUST be connected to
X5M/6 and X5M/4; the negative polarity to X5M/5 and
X5M/3.
1 Connect the electricity meters cable to the appropriate terminals
as shown in the illustration below.
X5M
S2S S3S
2 Fix the cable with cable ties to the cable tie mountings.
NC
21 29
X2M
X1M
M2S
EABH/X16DF6V+9W
Daikin Altherma 3 H W
4P644479-1 – 2020.12

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Eabh16df9wEabx16df6vEabx16df9w

Table des Matières