Installing The Outdoor Unit; Installing The Refrigerant Piping - Mitsubishi Electric Mr.SLIM PUHZ-HRP71HA2 Manuel D'installation

Masquer les pouces Voir aussi pour Mr.SLIM PUHZ-HRP71HA2:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 22

3. Installing the outdoor unit

M10 (3/8") bolt
Base
As long as possible.
Vent
Set deep in the ground
600
Min. 10

4. Installing the refrigerant piping

4.1. Precautions for devices that use R410A refrigerant
• Refer to page 3 for precautions not included below on using air conditioners
with R410A refrigerant.
• Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration oil
applied to the fl ared sections.
• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes,
to connect the refrigerant pipes. Use refrigerant pipes with the thicknesses
specified in the table to the below. Make sure the insides of the pipes are
clean and do not contain any harmful contaminants such as sulfuric com-
pounds, oxidants, debris, or dust.
Min. 360
600
175
175
950
Fig. 3-1
(mm)
• Be sure to install the unit in a sturdy, level surface to prevent rattling noises
during peration. (Fig. 3-1)
<Foundation specifi cations>
Foundation bolt
Thickness of concrete
Length of bolt
Weight-bearing capacity
• Make sure that the length of the foundation bolt is within 30 mm of the bottom
surface of the base.
• Secure the base of the unit fi rmly with four-M10 foundation bolts in sturdy loca-
tions.
Installing the outdoor unit
• Do not block the vent. If the vent is blocked, operation will be hindered and
breakdown may result.
• In addition to the unit base, use the installation holes on the back of the unit to
attach wires, etc., if necessary to install the unit. Use self-tapping screws (ø5 ×
15 mm or less) and install on site.
Warning:
• The unit must be securely installed on a structure that can sustain its
weight. If the unit is mounted on an unstable structure, it may fall down
and cause damage or injuries.
• The unit must be installed according to the instructions in order to mini-
mize the risk of damage from earthquakes, typhoons, or strong winds. An
incorrectly installed unit may fall down and cause damage or injuries.
Warning:
When installing or moving the air conditioner, use only the specifi ed refriger-
ant (R410A) to charge the refrigerant lines. Do not mix it with any other refrig-
erant and do not allow air to remain in the lines. Air enclosed in the lines can
cause pressure peaks resulting in a rupture and other hazards.
Liquid pipe
Gas pipe
• Do not use pipes thinner than those specifi ed above.
M10 (3/8")
120 mm
70 mm
320 kg
HRP71,100,125
ø9.52 thickness 0.8 mm
ø15.88 thickness 1.0 mm
5

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Mr.slim puhz-hrp100ha2Mr.slim puhz-hrp125ha2

Table des Matières