Télécharger Imprimer la page

Eaton CROUSE-HINDS GHG 627 Série Mode D'emploi page 12

Publicité

Les langues disponibles

Les langues disponibles

1.3
Undervoltage release (UA)
D1
UA
D2
Typ: GHG627 7 ...
Rated control voltage (U
):
s
AC 50 / 60 Hz
DC
Operating range:
Drop-out voltage
x U
s
Pull-in voltage
x U
s
Power consumption:
AC
Pull-in power
Holding power
DC
Pull-in power
Holding power
Max. opening time:
Minimum command time:
1.4
Shunt release (AL)
C1
AL
C2
Typ: GHG627 7 ...
Rated control voltage (U
):
s
AC 50 / 60 Hz
DC
Frequency range:
Operating range:
AC 50 / 60 Hz
x U
s
DC
x U
s
Power consumption:
AC
Pull-in power
Holding power
DC
Pull-in power
Holding power
Max. opening time:
Minimum command time:
12
Explosion-protected circuit breakers, series GHG 627 7 .. R....
R 0 ...
24 ... 525 V
-
0.35 ... 0.7
0.85 ... 1.1
1.5 VA
1.5 VA
0.8 VA
0.8 VA
19 ms
10 - 15 ms
R 0 ...
24 ... 440 V
24 ... 440 V
0 ... 400 Hz
0.7 ... 1.1
0.7 ... 1.1
2.5 VA / W
2.5 VA / W
2.5 VA / W
2.5 VA / W
20 ms
10 - 15 ms
R 1 ...
24 ... 525 V
24 ... 250 V
-
-
1,5 VA
1,5 VA
2,5 VA
2,5 VA
R 1 ...
24 ... 440 V
24 V
-
-
-
50 VA
50 VA
50 VA
50 VA
-
-
GB