EME6X40MC
MultiChannel Power/Energy Meter
One Voltage / Six Currents CT Connected 40 A, for Residential Loads Monitoring
Lateral IR Interface for Optional Communication
• The MultiChannel Meter measures the Line Voltage of a
single phase electrical installation and a maximum
of 6 currents, that are assumed to be powered by the
measured voltage itself. The currents are measured by
means of dedicated external CTs, that have a primary
maximum applicable current of 40 A.
No other current wiring connection system is allowed (direct
connection is forbidden; the usage of other CTs are not
recommended).
RISK OF ELECTRIC SHOCK, BURNS OR EXPLOSION
This device must be installed and maintained ONLY by qualified and duly authorized personnel.
Ordering information
Code
Art. Nr.
Description
EME6X40MC
186959
Multi-Channel Power/Energy Meter
• Scroll key selects the channel (rotating).
The number of the channel is displayed in the first digit (1 to 6, and then "T" for the totalized virtual meter)
• These keys select (rotating) one of the following group of
and
values:
- Active Energy (kWh)
- Reactive Energy (kvarh)
• By pushing together "
" and "
" keys, it is possible to reset the accumulated energies (a password is required)
Example of Display Pages
• Each row of the menu is dedicated to a meter (1 to 6 and "T" for "total"). Each column is a group of data.
Energy Reset procedure
• In any of the menu page, by pushing together "
" and "
• meaning that a password is required
• The password is a sequence of 4 key pushing (single key push and release). At each pushing, a 0 appears instead of "
• After the 1st key pushing
• After the 3rd key pushing
• The correct sequence is
• 1st key
• 2nd key
• Any other combination of keys is not accepted.
• 3rd key
Once the "reset?" question appears, if the user really wants to reset all energies, it must push again"
then the energies are zeroed. If, in any step of the procedure, no keys is pushed for more than 10 seconds, the display goes
• 4th key
back to the energy/power representation pages, without resetting any energies
Operating instructions
Every 1 seconds, it calculates, the following values:
- Active Energy - Reactive Energy
- Active Power - Reactive Power
for each of the measured current channel.
The powers, and, consequently, the Energy, are sign-less
(the device measures their absolute value), meaning that
whichever the wiring connection maybe, the power flow is
assumed to go from the net to the load(s). In this way, the
installer is not required to take care about the "versus"
of the currents and of the voltage.
During its installation, be sure there is no voltage applied.
Manual must be consulted
Display
• Energy value
• kWh / kvarh display
• Metrological LED pulsing at 1000 p/kWh (of the total power)
Commands
- Active Power (kW)
- Reactive Power (kvar)
Pushing the
key
Pushing the
key
" keys, the following page will appear:
", like reported below
• After the 2nd key pushing
• After the 4th key pushing,
assuming that the sequence
is correct.
.
Dimension
Technical Data
Data in compliance with EN 61010-1 and EN 61010-2-030
General characteristics
• Housing according to
03/17 IL145001ZU
• Mounting
• Depth
• Weight
Voltage Circuit (Supply and Measure)
• Reference Voltage
• Supply Current
• Supply and Measuring range
• Maximum power dissipation
• Operating and Measuring Voltage Frequency
• Voltage Waveform AC
Current Circuit (6 channels)
(at device current input terminals)
• Measuring Current full range at secondary side of external CTs
• Maximum applicable Current at secondary side of external CTs
(at primary side of external CTs)
• Reference Current (Iref)
• Minimum Current (Imin)
• Maximum Current (Imax)
• Starting Current (Ist)
Energy Accumulation Accuracy
• Active Energy Accuracy
according to EN 50470-3
• Reactive Energy Accuracy according to EN 62053-23
Measuring Features (including errors of external 0.2s CTs)
• Voltage
- specified Measuring range
- fundamental Voltage Frequency range
- accuracy (inside voltage and frequency range)
• Current (6 channels)
- specified Measuring range (referred to CTs primary)
- accuracy (inside the specified range)
• Active, Reactive and Apparent Power
- specified Measuring range (referred to CTs primary)
- accuracy (inside the measuring range)
Overload capability
• Voltage
- continuous, phase to Neutral
- temporary, 1 second phase to Neutral
• Current (at input terminals)
- continuous
Display
• Refresh period
Optical metrological LED
• Front mounted red LED (meter constant)
Safety
• Protective class
• Measurement
• Overvoltage
• AC voltage test
• Degree of pollution
• Operational voltage
• Impulse voltage test
• Housing material flame resistance
• Risk Assessment availability
Connection terminals
• Screwdriver for mains terminals
• Terminal capacity main current paths
Environmental conditions (storage)
• Temperature range
Environmental conditions (operating)
• Temperature range
• Mechanical environment
• Electromagnetic environment
• Installation indoor in a cabinet by means of DIN rail
• Altitude (max.)
• Humidity
• IP rating
L
" once,
230 VAC
N
External CTs
• Class 0.2 S
• Maximum primary current
40 A (per CT)
• CT Ratio
1/1000
Eaton Industries GmbH, A-1210 Wien
DIN 43880
EN 60715
with maximum form factor
(including errors of external 0.2S CTs)
(including errors of external 0.2S CTs)
proportional to Total active Energy
UL 94
head with Z +/-
solid wire min. (max)
stranded wire with sleeve min. (max)
yearly average, not condensing
on 30 days per year (not condensing)
Wiring diagram
1
2
3
4
5
6
6
4 5
3
1 2
L
N
2 A
MCB
2P manual disconnect switch
17.7
fl 6
www.eaton.eu/ducumentation
ENGLISH
EME6X40MC
DIN
2 modules
35 mm
DIN rail
mm
70
g
200
VAC
115-230
mA
8
VAC
92 ... 276
VA (W)
%2, (%0.6)
Hz
45 ... 65
-
2
mA
50
mA
100
A
5
A
0.25
A
40
mA
20
class
A (2%)
class
2
Vrms
92 ... 276
Hz
45 ... 65
-
±0.5%
VAC
0.02 ... 40
mA
±5, ±1%
W / var / VA
14 ... 11040
W
±7, ±1%
VAC
276
VAC
300
mA
100
s
1
p/kWh
1000
class
II
category
III
category
III
kV
4
-
2
VAC
300
1.2/50 µs-kV
6
class
V0
-
yes
POZIDRIV
PZ2
mm
2
1 (4)
mm
2
1 (4)
°C
-25 ... +70
°C
-25 ... +55
-
M1
-
E2
-
yes
m
2000
%
75
%
95
-
IP20
Dimension
9.8
Cable length
400
Cable length
03/17 IL145001ZU