2.2
Intended use
This product is intended to detect water and to signal accumulations of oil
during monitoring of:
•
Collection facilities under storage tanks, burners or motors
•
Tanks with collection facilities which are not visible
•
Collection facilities below devices consuming oil
•
Manholes, pipe and cable ducts
•
Pump and control stations where oil can accumulate due to leaks or back-
flow
The product is suitable for liquids to which the material of the photoelectric
probe is sufficiently resistant.
•
Diesel fuel (DIN EN 590) and low-viscosity oils with flash points of > 55 °C
at atmospheric pressure and at temperatures of -10 °C to +60 °C in dry
rooms
•
Synthetic diesel fuels (GTL) as per EN 15940
•
Fuel oil EL
•
Unused and used motor oils (for example, SAE 15W-40), gearbox oils
and hydraulic oils, transformer oils and vegetable oils, hydrogenated veg-
etable oils (HVO)
•
AdBlue® (urea solution 32.5 %) as per DIN 70070/ISO 22241
•
Water, grey water
The owner or operator must ensure that the components and the overall sys-
tem meet all directives and regulations applicable at the installation site, for
example, the directives pertaining to water and waterways.
Leak detection system class III as per DIN EN 13160-1 and DIN EN 13160-4
as liquid sensor system in leak or interstitial spaces, as safety device as per
worksheet DWA-A 791 or leak detection system as per worksheet
DWA-A 779.
Any use other than the application explicitly permitted in these operating
instructions is not permitted and causes hazards.
Verify that the product is suitable for the application planned by you prior to
using the product. In doing so, take into account at least the following:
•
All directives, standards and safety regulations applicable at the installa-
tion site of the product
•
All conditions and data specified for the product
•
The conditions of the planned application
Information on safety