G
®
THERMASGARD
Calibratable surface-contact temperature measuring transducer THERMASGARD
switchable measuring ranges, continuous output, in an impact-resistant plastic housing with quick-locking screws, optionally with ⁄ without
display, cable sensor with a pipe feeder (ALTM 2), incl. strap.
The surface-contact sensor is used to detect the temperature on lines, pipes (e.g., cold and warm water) or on heating sections for heating control. The
sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.
TECHNICAL DATA
Power supply:
24 V AC ⁄ DC (± 10 %) for U variant 15...36 V DC for I variant, depending on working resistance, residual ripple stabilised ± 0.3 V
Working resistance:
R
a
Load resistance:
R
L
Power consumption:
< 1.0 VA ⁄ 24 V DC; < 2.2 VA ⁄ 24 V AC
Insulating resistance:
≥ 100 MΩ, at +20 °C (500 V DC)
Pt1000, DIN EN 60751, class B Perfect Sensor Protection at IP68) sensor external
Sensor:
Measuring ranges:
multi-range switching with 8 switchable measuring ranges, see table (other ranges optional)
with manual zero point correction (± 10 K)
ALTM 1: compact variant,
ALTM 2: detached sensor variant,
Deviation, temperature:
typically ± 0.2 K at +25 °C
Output:
0 - 10 V or 4...20 mA
Connection type:
2- or 3-wire connection
Cable connection:
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector (male, 5-pin, A-code) according to DIN EN 61076-2-101
Housing:
plastic, UV-resistant, material polyamide, 30 % glass-globe reinforced, with quick-locking screws
(slotted ⁄ Phillips head combination), colour traffic white (similar to RAL
housing cover for display is transparent!
Housing dimensions:
72 x 64 x 37.8 mm (Tyr 1 without display)
72 x 64 x 43.3 mm (Tyr 1 with display)
Sensor cable: :
ALTM 2: Silicone, SiHF, 2 x 0.25 mm²; KL = 1.5 m (optionally also
other lengths and measuring range limits, e.g., PTFE up to +250 °C
or glass fibre with steel mesh up to +350°C)
Sensor protection:
ALTM 2: pipe feeder made of stainless steel V4A (1.4571),
Ø = 6 mm, L = 50 mm
Electrical connection:
0.14 - 1.5 mm² via terminal screws
Process connection:
endless strap with metal tightener (included in the scope of delivery)
Ø = 13 - 92 mm (¼ - 3"), L = 300 mm
Ambient temperature:
measuring transducer –30...+70 °C
Humidity:
< 95 % r. H., non-precipitating air
Protection class:
III (according to EN 60 730)
Protection type housing:
IP 65 (according to EN 60 529) Housing tested,
TÜV SÜD, Report No.713139052 (Tyr 1)
ALTM 2: IP 65 (according to EN 60 529)
Protection type sensor:
Standards:
CE conformity, electromagnetic compatibility according to
EN 61326, according to EMC directive 2014 ⁄ 30 ⁄ EU
Optional:
Two-line display with illumination, cutout approx. 36 x15 mm (W x H),
for displaying the ACTUAL temperature and the internal
diagnostics (measuring range exceeded, measuring range not
reached, sensor breakage, sensor short circuit)
®
THERMASGARD
ALTM 2 ⁄ ALTM 2 - Q
Type ⁄ WG01
ALTM 2
A LT M 2 - I
A LT M 2 - I LCD
A LT M 2 - U
A LT M 2 - U LCD
ALTM 2 - Q
A LT M 2 - I Q
A LT M 2 - I Q LCD
A LT M 2 - U Q
A LT M 2 - U Q LCD
Housing variant "Q":
Extra charge:
ACCESSORIES
WLP-1
ALTM
(ohm) = (U
-14 V) ⁄ 0.02 A for I variant, see working resistance diagram
b
> 5 kOhm for U variant
sleeve humidity-tight (standard)
IP 68 (according to EN 60 529)
sleeve water-tight (optional)
Surface contact ⁄ tube contact temperature measuring transducers
Sensor
Output
(with cable gland)
Pt1000
4...20 mA
Pt1000
4...20 mA
Pt1000
0 -10 V
Pt1000
0 -10 V
(with M12 connector)
Pt1000
4...20 mA
Pt1000
4...20 mA
Pt1000
0 -10 V
Pt1000
0 -10 V
Cable connection with M12 connector (male, 5-pin, A-code)
Other ranges optional, Protection type IP 68 (Sensor sleeve watertight compound-filled)
2-wire connecting leads, per running meter (silicone / PTFE / glass fibre)
Heat-conductive paste, silicone-free
®
ALTM 1 (compact variant) and ALTM 2 (detached variant) with eight
T
up to +100 °C,
operating range –50...+100 °C
max
T
over +100 °C,
operating range –50...+150 °C
max
Type
Remote sensor
Remote sensor
Remote sensor
Remote sensor
Remote sensor
Remote sensor
Remote sensor
Remote sensor
9016),,
Display and internal diagnostics
Display
Item No.
= Q
1101- 1122- 0219-920
■
1101- 1122-2219- 920
1101- 1121-0219- 920
■
1101- 1121-2219- 920
2001- 2121-2100- 001
■
2001-2122 -2100- 001
2001- 2121-1100- 001
■
2001-2122 -1100- 001
on request
7100- 0060-1000- 000
Rev. 2021 - V17
Standard
Measuring range
exceeded
Measuring range
not reached
Sensor
breakage
Sensor
short circuit