Troubleshooting; Warning Codes - Scb-01; Blocking Codes - Scb-01; Locking Codes - Scb-01 - BDR Thermea Group SCB-01 Notice D'utilisation Et D'installation

Carte d'extension
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 14
5

Troubleshooting

5.1

Warning codes - SCB-01

Tab.15
Warning codes
Code
Display text
A02.55
Inval or miss SerNR
5.2

Blocking codes - SCB-01

Tab.16
Blocking codes
Code
Display text
H02.00
Reset In Progress
H02.02
Wait Config Number
H02.03
Conf Error
H02.05
CSU CU mismatch
H02.18
OBD Error
H02.48
Funct Gr Conf Fault
H02.50
Funct Gr Comm Err
5.3

Locking codes - SCB-01

Tab.17
Locking codes
Code
Display text
E02.04
Parameter Error
E02.15
Ext CSU Timeout
7741254 - v.01 - 22112019
Description
Invalid or missing device serial
number
Description
Reset In Progress
Waiting For Configuration Number
Configuration Error
CSU does not match CU type
Object Dictionary Error
Function Group Configuration Fault
Function Group Communication
Error
Description
Parameter Error
External CSU Timeout
Solution
Contact your supplier.
Solution
Reset procedure active:
No action
Configuration error or unknown configuration
number:
Reset CN1 and CN2
Configuration error or unknown configuration
number:
Reset CN1 and CN2
Configuration error:
Reset CN1 and CN2
Reset CN1 and CN2
See
The data plate for the CN1 and CN2
values.
SCB not found:
Carry out an auto-detect
-
Solution
Configuration error:
Reset CN1 and CN2
See
The data plate for the CN1 and CN2
values.
CSU time out:
Bad connection: check the wiring and connec­
tors
Faulty CSU: Replace CSU
en
5 Troubleshooting
13

Publicité

Table des Matières
loading

Table des Matières