Technical specifications
Technical specifications
EN
Slots type EN 60 320/C19
No. of circuit-breakers
Electromagnetic circuit-breaker
Slots individually switchable
Connector, PDU input
Length of connection cable
Connection cable type
No. of wires
Cable cross-section
PDU enclosure width
PDU enclosure depth
PDU enclosure height (length)
PDU material
PDU mounting adaptor
Measurement func-
tions (input/phase out-
put slot)
Operating hours meter
34
Values recorded
Voltage measurement range
Voltage resolution
Voltage accuracy
Current measurement range
Current resolution
Current accuracy
Frequency accuracy
Active power (kW) accuracy
Apparent power (VA) accuracy
Active energy (kWh) accuracy
Power factor accuracy
Freely settable limit values for
warning/alarm
Rittal PDU international/PDU UK power distribution unit
Quantity depends on version, see section 8.2 "Al-
location of fuses, phases and slots"
2 (single-phase) or 6 (3-phase) with 32 A version, 12
(3-phase) with 63 A version
16 A, type C (only with 32 A versions)
Yes (not for PDU metered) (bistable relay, minimal in-
herent consumption)
EN 60 309/CEE (depending on PDU version),
EN 60 320/C20 for 7955.201/.301/.401,
BS 1363 UK plug for 7955.520/.530/.540/.940
3 m
H05-VV
3/5 (single-phase/3-phase PDU)
2.5 mm²/4.0 mm² (for 16 A/32 A versions)
44 mm (1 U), not for 7955.238
62 mm for PDU metered
85 mm for PDU switched, PDU managed and slave
PDU managed
Depends on product variant
Aluminium, anodised in RAL 9005 (black)
Plastic, black
Voltage (V), current (A), frequency (Hz), active power
(kW), active energy (kWh), apparent power (VA),
power factor, neutral-conductor measurement /
load imbalance detection, fuse monitoring (for 32 A/
63 A versions)
90 V...260 V
0.1 V
2%
0...16/32/63 A (depending on PDU variant)
0.1 A
2%
2%
2%
2%
1%
2%
Yes