CMC III/PDU sensor Model No: DK
9343.070
9343.170
9343.270
9343.370
The following CAN bus connection cables from the CMC III accessories range may be used:
CMC III/PDU sensor connection cable
Model No: DK
7030.090
7030.091
7030.092
7030.093
7030.094
7030.095
Connect one of the above sensors from the accessories range to the CAN bus interface of the PDU
using a CAN bus connection cable (fig. 15, item 2).
After connecting a sensor, the sensor software will be updated first of all, if necessary. The status
LED of the sensor remains continuously blue and also flashes purple during the entire update pro-
cess. In addition, the status LED of the PDU flashes white, and a corresponding message appears
on the website.
Status change display following completion of an essential update:
– The two green and the two red CAN bus LEDs on the CAN bus connection of the connected sen-
sor will start to flash.
– The multi-LED of the PDU flashes continually in the sequence green – orange – red.
– The multi-LED of the connected sensor flashes blue continuously.
Confirm the newly connected sensor on the PDU website.
Alternatively, the newly connected sensor can also be confirmed locally via the display. To do this:
In the Rittal main menu, select the "Setup" entry and confirm your entry by pressing the "Return" key.
Select the "Sensor" entry and press the "Return" key to confirm your selection. The menu for entering
your security PIN will appear.
Enter the required security PIN (see section 6.1 "Settings via the display") then confirm the entry "Ac-
knowledge All Devices" by clicking on "Return".
Status change display on the CAN bus LEDs:
– Continuous green LEDs: CAN bus status "OK".
– Continuous red LEDs: CAN bus status faulty.
Status change display on the multi-LED of the PDU:
– Continuous green light: The PDU and all devices connected to the CAN bus have the status "OK".
– Continuous orange light: The PDU or at least one device connected to the CAN bus has the status
"Warning".
– Continuous red light: The PDU or at least one device connected to the CAN bus has the status
"Alarm".
Rittal PDU international/PDU UK power distribution unit
Settings of the PDU metered/switched/managed
Description
NH measurement module NH00, 150 A
NH measurement module NH 1, 250 A
NH measurement module NH 2, 400 A
NH measurement module NH 3, 600 A
Description
CAN bus cable (2 x RJ 45) length: 0.5 m
CAN bus cable (2 x RJ 45) length: 1 m
CAN bus cable (2 x RJ 45) length: 1.5 m
CAN bus cable (2 x RJ 45) length: 2 m
CAN bus cable (2 x RJ 45) length: 5 m
CAN bus cable (2 x RJ 45) length: 10 m
EN
31