Dipswitch Settings
Inducer OFF / Heat ON
(Blower) Delay (sec)
SW1-1
5 / 45*
1
2
3
4
OFF
ON
15 / 66
1
2
3
4
OFF
ON
*Default
NOTE:
SW 1-1 selects both the inducer OFF delay and heat ON delay simultaneously. For example, the default setting
(switch ON) sets the inducer OFF delay to 5 seconds and the Heat ON delay for the blower to 45 seconds.
Enter Self-Test immediately after control
power up by:
• Double pressing the "FAULT RECALL" button while
LED rapid flashes green.
NOTE: Control will terminate Self-Test mode if any
system fault occurs. Control will ignore any active
thermostat calls during Self-Test.
• Sequence is as follows:
• LED will flash all stored fault codes five times. If there
are no faults, the LED will be off for 2 seconds.
• Afterward, the LED will slowly flash code 11 in alternate
Constant Fan Speed
SW1-2
1
2
LO/HEAT*
3
4
OFF
ON
1
2
FAN
3
OFF
4
OFF
ON
Heat OFF (Blower) Delay (sec.)
SW1- 3 & 4
1
2
3
225
225
4
OFF
ON
1
2
3
135*
4
OFF
ON
colors (green, amber, red) to indicate Self-Test is
active. This will continue until Self-Test is complete.
• Inducer motor will turn ON and continue running until
Self-Test is complete.
• After 15 seconds, the ignitor will turn ON for 15 seconds,
then OFF.
• Blower motor runs at the Fan (SW1-2), Heat, and Cool
speeds respectively for 10 seconds each.
• Blower and Inducer motors turn OFF.
• Self-Test is complete, LED will display solid green to
indicate Standby mode.
CONFIGURATION
1
2
3
180
180
4
OFF
ON
1
2
3
90
4
OFF
ON
SELF TEST