The illustration below show examples of free-topology wiring. The LMIO-102 device communicates to all other Digital Lighting
Management devices connected to the low voltage DLM Local Network, regardless of their position on the DLM Local Network.
Switch
LMRJ Cables
Low Voltage Wires
Occupancy Sensor
OPERATION
The LMIO-102 device allows a DLM system to automatically
reconfigure the DLM devices in a space that has up to four
moveable walls. Each combination of walls being Open or
Closed is called a Profile in the DLM system, the LMIO-
102 device transitions the system from profile to profile as
the walls get closed or opened. Commissioning of spaces
containing moveable walls is done using the standard Push
n' Learn concept used in regular spaces, the difference is
that Push n'Learn needs to be repeated as many times as
the number of profiles expected. For example, if there is one
wall, then Push n'Learn needs to be performed in the room 2
times (when the wall is open and when the wall is closed - so
there are 2 profiles being used).
Once all devices, including the LMIO-102, are installed,
proceed with the following steps to configure the system for
each of the profiles expected. Note that if the LMPS-104 is
also present in the same room, it will just act as a display
device. The LED on the button corresponding to the wall that
has been closed will light up. The contact door as sensed by
the LMIO-102 device has a higher priority over button press.
1. Reconfigure the space for a specific profile by Opening
or Closing the walls to represent one of the ways the
space will be used as. Note that the LEDs on the
LMIO-102 will light up representing when a wall is
closed, otherwise the corresponding LED will be Off.
2. Enter into Push n' Learn mode from any device and
configure the individual spaces so that the occupancy
sensors and switches get bound to the appropriate
loads that belong to the same space. Refer to the
LMSW-10x QSG and follow Step 1 for instructions on
how to enter Push n' Learn. Note also that only profile
1 (all walls open) will have default bindings that follow
Plug n' Go rules, all other profiles will have no bindings
per default.
3. Exit Push n' Learn.
Follow the above steps for each additional profile.
CAUTION: TO CONNECT A COMPUTER
TO THE DLM LOCAL NETWORK USE
THE LMCI-100. NEVER CONNECT
THE DLM LOCAL NETWORK TO
AN ETHERNET PORT – IT MAY DAMAGE
COMPUTERS AND OTHER CONNECTED EQUIPMENT.
Line Voltage
Room
Controller
Input from Wall Contact
Closures
LMIO-102
Partition Interface
CONNECTIVITY
Loads
1
2
The LMIO-102 accommodates up to 4 movable walls representing
a total of 16 different configurations (profiles). For each of these
profiles, there is a "Load Table" that contains the binding information
between the switch/sensor and the load in the local IRB. The
following table lists the 16 different profiles:
Profile
Room A
P1
A + B + C + D + E
P2
A
P3
A + B
P4
A
P5
A + B + C
P6
A
P7
A + B
P8
A
P9
A + B + C + D
P10
A
P11
A + B
P12
A
P13
A + B + C
P14
A
P15
A + B
P16
A
2
RJ45 ports (2)
Configuration LED
Configuration
push button
LEDs (5)
Wall
Wiring Terminals
Buttons and Indicators
LOAD PROFILES
WALL 1
WALL 2
WALL 3
Room B
Room C
Room D
B + C + D + E
C + D + E
B
C + D + E
D + E
B + C
D + E
C
D + E
B
C
D + E
B + C + D
C + D
B
C + D
D
B + C
D
C
D
B
C
D
WALL 4
Room E
E
E
E
E
E
E
E
E