Function and features
The T6 dual sensor is a slave in the AS-i system (AS-i profile S7.A.E).
It is designed for use on pneumatic valve actuators. It energises the
solenoid of the pneumatic valve and provides position feedback from
the actuator.
• Sensor and actuator supply as well as data transfer to the controller
via AS-i 2-wire cable
• Watchdog function: If the connection to the master is interrupted
for more than 40ms, the output is switched off (logically 0) when
the master messages fail
• Diagnostic information via red flashing LED (short circuit or open cir-
cuit)
• max. number of modules per master: 62
• AS-interface version 2.1
• Operating voltage 26,5 ... 31,6V DC
• Current consumption <260mA
• The outputs must not be set simultaneously
Operation and display elements
1 2
10
9
8
1: M12 plug
6: valve plug 1
2: T6 dual sensor
7: valve plug 2
3: sensor area
8: Y cable
4: puck
9: M12 socket
5: standard actuator
10: AS-i flat cable
Fonctionnement et caractéristiques
Le capteur double T6 est un esclave AS-i (profil AS-i S7.A.E). Il est
conçu pour l'utilisation sur des actionneurs de vannes. Il permet la
commande d'une vanne et la détection de sa position.
• alimentation des capteurs, de l'actionneur et de l'électrovanne à l'ai-
de du câble AS-i 2 fils
• fonction chien-de-garde: Si la communication avec le maître est
interrompue ou défaillante plus de 40ms, la sortie est désactivée
(niveau logique 0)
• informations diagnostiques par LED rouge clignotante (court-circuit
ou rupture de câble) et bit de donnée
• Nombre maxi de modules de sécurité par maître: 62
• version AS-interface 2.1
• tension d'alimentation 26,5 ... 31,6V DC
• consommation <260mA
• Les sorties ne doivent pas être activées en même temps
Eléments de service et d'indication
1 2
10
8
9
1: M12 fiche mâle
2: capteur double T6
3: zone active
4: came porte drapeau
5: vanne standard
3 4
5
7
6
3 4
5
7
6
6: connecteur pour électrovanne 1
7: connecteur pour électrovanne 2
8: câble en Y
9: M12 fiche femelle
10: câble plat AS-i
Installation
Address the T6 dual sensor with an addressing unit, address „0" is set
at the factory. Fasten it to the valve fixings according to the standards
(ISO 5211 VDI/VDE).
Connect the solenoid valve to the M12 socket. Only solenoid valves
with a nominal voltage of 24V and a power of up to max. 2.4W may
be connected.
Data bits
Data bit
Type
D0
input
D1
input
D2
input
D3
input
D0
output
D1
output
Connection
M12 plug
pin
4
3
AS-i +
AS-i -
1
2
Operation
Check the safe functioning of the unit. Display by LEDs.
• LED red flashing: short circuit or open circuit in one output
• LED is lit: no communication with the master
• Yellow LED is lit: function display (input and output signals are dis-
played)
Montage
Adresser le capteur double T6 à l'aide d'une unité d'adressage
(l'adresse „0" étant présélectionnée à l'usine). Le fixer sur la vanne
selon les normes (ISO 5211 VDI/VDE).
Raccorder l'électrovanne sur la fiche femelle M12. Uniquement pour
des électrovannes d'une tension nominale de 24V et d'une puissance
de 2,4W maxi.
Affectation des bits de données
Bit de données
Type
D0
entrée
D1
entrée
D2
entrée
D3
entrée
D0
sortie
D1
sortie
Raccordement
Pin
M12 fiche mâle
4
3
AS-i +
AS-i -
2
1
Fonctionnement
Vérifier le bon fonctionnement du capteur double. Indication par LED.
• LED rouge clignote: court-circuit ou rupture de câble sur la sortie
• LED rouge allumée: aucune communication avec le maître
• LED jaune allumée: indication de fonctionnement (les signaux d'en-
trées et de sortie sont indiqués)
Designation
Description
sensor position1
sensor 1
damped
sensor position2
sensor 2
damped
open circuit
error actuator
at the actuator
short circuit
error actuator
at the actuator
switch output for
actuator
solenoid valve 1
switch output for
actuator
solenoid valve 2
M12 socket
pin
1
switch output +
4
3
voltage -
3
switch output +
2
Désignation
Description
position 1
capteur 1
de la vanne
position 2
capteur 2
de la vanne
rupture de câble
défaillance
sur l'actionneur
court-circuit
défaillance
sur l'actionneur
sortie de commutation
actionneur
pour électrovanne 1
sortie de commutation
actionneur
pour électrovanne 2
Pin
M12 fiche femelle
1
4
sortie de commutation +
3
tension -
3
2
sortie de commutation +
3
4
1
2
3
4
2
1