Product description, Assembly instructions, Installation and operation
3.2
Proper use
The PDU is intended to be used in particular for the distribution of power in IT racks.
EN
3.3
Operating conditions
The PDU is only allowed to be used under the following operating conditions:
Temperature application range:
Humidity application range:
Protection category:
Protection class:
Overvoltage category:
Degree of contamination:
max. operating height:
min operating time:
Approvals and environmental prop-
erties:
4
Assembly instructions
The PDU is assembled with the aid of the supports included in the accessories. The unit can be mount-
ed either at the front or rear, left or right of the IT rack.
Note:
Rittal recommends always first attaching the supports to the PDU and then fitting the two
together to the enclosure. In this way the distances between the supports and therefore
the fastening points in the enclosure are pre-defined and you can see if there is any risk
of collision of the PDU in the enclosure at an early stage.
Note:
Select the fastening point (position and distance) for the two universal supports in the en-
closure such that there is no risk of collision with the clips on the rear of the PDU.
5
Installation and operation
Connect the PDU to a TN-S or IT network:
Input voltage range L-N:
Input current:
Number of phases:
Colour coding of the phases/fuse
circuits (3-phase versions only):
Connection cable type:
Number of wires:
14
Temperature Operation: +5 °C...+50 °C (at 100% load))
Temperature Storage: -20 °C...+70 °C
10%...95% relative humidity, non-condensing
IP 20 to IEC 60 529
1
II
2
3,000 meters above sea level
100,000 h
Low-Voltage-Directive 2014/35/EU
EMC Directive 2014/30/EU
90 V to 250 V (400 V) AC, 50 Hz or 60 Hz
16 A (13 A) or 32 A, depending on the version
single or 3, depending on the version
L1: pink
L2: black
L3: white
H05-VV
3 (single-phase versions) or 5 (3-phase versions)
Rittal Power distribution Unit PDU basic