Installation
6.
Installation
6.1
Installation
1. Remove the door of the surface-mounted cabinet.
2. Adjust the feet of the surface-mounted cabinet
to the required height. Observe the height of the
screed when adjusting the feet. The screed surface
should be at least 1 cm above the lower edge
of the plinth. A height marking will appear when
extending the feet (see Illustr. 7 on page 20).
The dimensions on the height marking indicate the
distance between the floor and the lower edge of
the plinth. Adjust the feet by loosening the wing
nuts and fix them by tightening the wing nuts.
Illustr. 7: Height marking
3. Position the surface-mounted cabinet at the
designation installation location.
4. Fix the cabinet at the feet and the wall attachment
points (see Illustr. 1 on page 17 (1) and Illustr. 2
on page 17 (2)).
5. Fit the dwelling station and its accessories into the
surface-mounted cabinet. Observe the operating
instructions of the different components.
6. Refit the door of the surface-mounted cabinet.
You can use the cardboard for the protection of
the door during the construction phase.
20
Surface-mounted cabinet
6.2
Protective equipotential bonding/
Earthing
DANGER
Danger to life due to electric current!
Danger to life due to contact with live
components.
f Completely disconnect the station from
the power supply and protect it against
accidental restart.
f Check that no voltage is present.
f The electrical connection must only be
carried out by a qualified electrician.
Before commissioning of the installation, the surface-
mounted cabinet must be earthed via a protective
equipotential bonding conductor by a qualified
electrician according the valid standards and local
regulations. The surface-mounted cabinet must be
connected to the equipotential bonding rail of the
building via the central earthing point. The required
equipotential bonding cable made of copper has to
feature a minimum cross section of 6 mm² . Observe
the DIN VDE 0100-540 standard.
Illustr. 8: Earthing of the door
(1)
Central earthing point
(2)
Earthing point of the door
Accessories for earthing of the door are
supplied with the surface-mounted cabinet.
Earthing of the dwelling station "Regudis
W-HTE" and its accessories is carried out via
the earthing of the cabinet.
1
2
134469780-V03.04.2019