The indoor unit must be installed such that there is no short
circuit of the cool discharge. Respect the installation clearance.
Do not put the indoor unit where there is direct sunlight on
unit. The location is suitable for piping and drainage and it
must have a large distance between a door and unit.
Ceiling Concealed Mounting
• Use the hanger supplied with the unit.
• Make sure that the ceiling is suffi ciently strong to withstand
the weight.
See Detail A
Insulation material
(fi eld supply)
Air outlet side
Aluminium tape
(fi eld supply)
Detail A
Ceiling Concealed Drain Piping Work
• The drain pipe must be installed as shown in the diagram (see diagram above) to avoid damage caused by leaks and
condensation.
• For the best result, keep the piping as short as possible. Slant the piping at an angle to improve the fl ow.
• Ensure the drain pipe is securely insulated.
• It is necessary to provide a drain trap in the drain outlet to relieve pressure that exists within the unit compared to the outside
atmospheric pressure when the unit is operating. The drain trap is to avoid possibility of splashes or an odor.
• Keep pipes as straight as possible for easy cleaning and to prevent the accumulation of dirt and debris.
• Conduct a water drainage test after the installation is completed. Make sure that the drainage fl ow is smooth.
• In humid environments, use an extra drain pan to cover the entire area of the indoor unit.

INSTALLATION OF THE INDOOR UNIT

Air inlet side
Aluminium tape
(fi eld supply)
Field supply
Washer for hanger
bracket (attached)
Tighten
Center distance of axle (see drawing below)
* Can be smaller than 300mm if ceiling is removable.
ABQ
71 BV 1
100 AV 1
125 AV 1
140 AV 1
Provide clearance for servicing ease and optimal air fl ow as
shown in the diagram.
1-4
A
L
300mm
or more
300mm* or more
Ceiling
2300mm or more
A mm (inch)
L mm (inch)
959 (37.8)
339 (13.3)
1264 (49.8)
401 (15.8)
1326 (52.2)
266 (10.5)
1526 (60.1)
266 (10.5)
Floor
Unit : mm