MICROWAVE SENSOR - PARAMETER SETTINGS
Detection range (sensitivity)
This determines the effective range of the motion detector and is set by DIP switches at the sensor itself, refer to figure. Note that reducing
the sensitivity will also narrow the detection range.
The following settings are available:
I
Detection range 100%
II
Detection range 75%
III
Detection range 50%
IV
Detection range 25%
V
Detection range 10%

Time setting

This determines the time the fitting remains at 100% level on motion detection and is set with DIP switches at the sensor itself, refer to figure.
The walk test setting is useful when installing the fixture to establish correct operation on range.
The following settings are available:
I
5s (walk test)
II
30s
III
1 min
IV
5 min
V
15 min
VI
30 min
Light control setting
This setting holds off the 100% light output should there be sufficient daylight and is set using DIP switches at the sensor, refer to figure.
The following settings are available:
I
2 Lux - darkness mode only
II
5 Lux - twilight mode
III
10 Lux - twilight mode
IV
30 Lux - daylight mode
V
50 Lux - daylight mode (walk test)
VI
Daylight sensor disabled
Please set 'Disable' to have High-low light function in the evening.
See page 15 - Cable connection LED driver.
10
Detection area
Hold time
Daylight sensor
www.prolumia.com