Spare Parts; Accessories - Honeywell D05F Notice De Montage

Masquer les pouces Voir aussi pour D05F:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 8
10. Disposal
• Dezincification resistant brass housing
• Brass threaded connections
• High-quality synthetic material valve insert
• Stainless steel fine filter mesh
• High-quality synthetic material spring bonnet with adjust-
ment knob and setting scale
• Spring steel adjustment spring
11. Troubleshooting
Problem
Beating sounds
Water is escaping from the spring
bonnet
Too little or no water pressure
The outlet pressure set does not
remain constant

12. Spare Parts

No. Description
1
Spring bonnet complete
with setting scale
2
Valve insert complete
(without filter)
3
Replacement filter insert
4
Blanking plug
with O-ring R
/
"
1
4
(5 pcs.)
MU1H-1019GE23 R0412
Cause
Pressure reducing valve is too
large
Diaphragm in valve insert is faulty
Shutoff valves up- or downstream of the
pressure reducing valve are not fully open
Pressure reducing valve is not set to the
desired outlet pressure
Filter in pressure reducing valve is conta-
minated
Pressure reducing valve is not fitted in flow
direction
Filter in pressure reducing valve is conta-
minated or worn
Valve insert, sealing ring or edge of nozzle
is contaminated or worn
Rising pressure on outlet (e.g. in boiler)
Dimension Part No.
/
" - 1"
0901515
1
2
/
" - 1"
D05FA-1/2B
1
2
/
" - 1"
ES05F-1/2A
1
2
/
" - 1"
S06K-1/4
1
2
GB
• Fibre-reinforced NBR diaphragm
• NBR seals
Observe the local requirements regarding correct waste
recycling/disposal!
Remedy
Call our Technical Customer Services
Replace valve insert
Open the shutoff valves fully
Set outlet pressure
Clean or replace filter
Fit pressure reducing valve in flow direction
(note direction of arrow on housing)
Clean or replace filter
Replace valve insert
Check check valve, safety group etc.

13. Accessories

M38K
Pressure gauge
Housing diameter 50 mm, below connection thread
G1/4". Ranges: 0 - 4, 0 - 10, 0 - 16 or 0 - 25 bar.
Please indicate upper value of pressure range when
ordering
ZR06K
Double ring wrench
For removal of spring bonnet
VST06-A Connection set
Threaded connections
VST06-B Connection set
Solder connections
7
Honeywell GmbH

Publicité

Table des Matières
loading

Table des Matières