Parameters
Regulation and control
SP Temperature setting (Set Point)
CE SELFDRIVE Mode 0=Deactivated 1= Activated
C0 Sensor 1 calibration (Offset)
C1 Sensor 1 differential (Hysteresis)
Set point top locking
C2
(it cannot be set above this value)
Set point bottom locking
C3
(it cannot be set under this value)
Type of delay for the protection of the compressor:
C4
0=Minimum OFF time of the compressor
1=Minimum OFF and ON time of the compressor in each cycle
Protection delay time
C5
(Value of the option selected in parameter C4)
COOL relay status with fault in sensor 1:
C6
0=OFF; 1=ON; 2=Average according to last 24 h before the sensor error;
3=ON-OFF according prog. C7 and C8
Time of relay ON if sensor 1 damaged
C7
(If C7=0 and C8¹0, the relay will always be OFF when disconnected)
Time of relay OFF if sensor 1 damaged
C8
(If C8=0 and C7¹0, the relay will always be ON when connected)
C9 Maximum duration of the continuous cycle mode. (0=deactivated)
Variation of the Set Point (SP) in continuous cycle mode. When it reaches this
C10
point (SP+C10), it reverts to the normal mode. (SP+C10 ³ C3).
The value of this parameter is always negative, unless it is 0. (0=OFF)
Variation of the set point (SP) when the change set point change function is
C12
active. (SP+C12£ C2) (0= deactivated)
Maximum time for start-up after gas collection
C19
(Values between 1 and 9 seconds are not accepted) (0= Deactivated)
C20 Maximum time for pump down (0= deactivated)
C22 Stop fans and COOL when opening door 0=No 1=Yes
C23 Start-up delay for fans and COOL when door open
C24 Delay time of cold stop with door open.
C25 Influence of probe S3 when regulating with two temperature probes (I20=10)
C27 Sensor 4 calibration (Offset)
EP
Output to level 1
**In Selfdrive mode
Description
29
3516526A11 Ed. 01
Values Min. Def. Max.
ºC/ºF
-50 0.0 99
0
1
1
ºC/ºF -4.0 0.0 4.0
ºC/ºF
1.0 2.0 20.0
ºC/ºF
C3
99
99
ºC/ºF
-50 -50 C2
0
0
1
min.
0
0
120
0
2
3
min.
0
10 120
min.
0
5
120
h.
0
0
48
C3-
ºC/ºF
0
-50
SP
C3-
C2-
ºC/ºF
0
SP
SP
sec.
0
0
120
min.
0
0
15
0
0
1
min.
0
0
999
sec.
0
0
C23
%
0
0
95
ºC/ºF -4.0 0.0 4.0