10. Electrical Connection

Output characteristic
Connecting the output lines
Apply wire-end ferrules to flexible lines
10.1 Connect the cores of the output line according to the pin configuration on the T-
junction or on the fitting.
SELV power supply - pin configuration
Pin P1
Signal
1
Not used
2
Not used
3
GND
4
Not used
5
24 V
10.2 Connect the output line to the compact system power supply.
10.3 Insert the power plug into the socket.

11. Fault correction

Fault
No output voltage
present
If you are unable to correct a fault or if the fault is not described in the fault correction
section, please inform our service department!
Level
0 V
24 V +
Cause
– Voltage supply interrupted
– Compact system power supply
defective
– Output load too high (possibly short
circuit)
Curren
Colour C1
t
yellow
green
white
brown
0.5 A
red
Remedy
➯ Restore
➯ Replace
➯ Eliminate the
source of the fault
on the connected
components