Technical Specifications - HYDAC ELECTRONIC CSI-B-2 Notice D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

User Manual CSI-B-2

6. Technical specifications

Input data
HSI interface
Output data
Signal output
Ambient conditions
Operating temperature range
Storage temperature range
Relative humidity
mark
Protection class to DIN 40050
Other data
Supply voltage of the module
(male connection X1)
Current capacity (module + sensor)
Sensor supply
(male connection X2)
Electrical connection:
X1 : module supply + RS232 / RS485
X2 : sensor supply + HSI
SUB-D: RS232
Reverse polarity protection of the supply
voltage, excess voltage, override and short
circuit protection
Option of conversion mode
Indication of active conversion mode
Housing
Weight
8
HYDAC Sensor Interface
For linking sensors digitally
- male connection X2
switchable:
RS 485 half-duplex or
RS 232
- male connection X1
- SUB-D 9 pole connection (RS232)
-25 .. +85 °C
-30 .. +85 °C
0..70%, non-condensing
EN 61000-6-1, EN 61000-6-2,
EN 61000-6-3, EN 61000-6-4
IP 40
18 .. 35 V DC
30 mA to 300 mA max.
(depending on the supply voltage and the
sensor connected)
15 V DC ± 5% / 300 mA max. at 23 °C
15 m max. cable length
Max. cross-section of connection 1.5 mm²
Male terminal block, 8 pole RM 3.5
Male terminal block, 5 pole RM 3.5
(see table pin connections)
9 pole connection with securing screws
provided
Option of HSI - RS232 or HSI - RS485
via jumper (bridge):
X1.3 - X1.4 open:
X1.3 - X1.4 closed: HSI - RS485
Green LED:
HSI - RS232
Yellow LED:
HSI - RS485
Dimensions : 55 x 105 x 31 mm
Housing to be mounted on rails (35mm)
to DIN EN 60715 TH 35
(formerly DIN EN 50022)
approx. 140 g
02/06/2009
HSI - RS232