The functions require a sinusoidal load. The MOTUS®
mu t therefore not be u e
irectly up tream or
own tream of frequency inverter .
To ensure correct function, current must not be
allowed to fl ow "past" the MOTUS® to the motor. No
strong electrostatic backfl ow is allowed from the
load side back to the MOTUS®. In ulation fault or

2. Pro uct table

Type MOTUS®ContactronControl, irect an rever ing tarter
for Sy tem 30Compact
for 12 × 5mm and 12 × 10mm busbars
Type 0.075 – 0.6A
Type 0.18 – 2.4A
Type 1.5 – 9A
for Sy tem 60Cla ic
for 12 × 5 – 30 × 10mm busbars, double-T and triple-T sections
Type 0.075 – 0.6A
Type 0.18 – 2.4A
Type 1.5 – 9A
for DIN rail mounting
according to DIN EN 60715
Type 0.075 – 0.6A
Type 0.18 – 2.4A
Type 1.5 – 9A
Acce orie
Plug connector with cable connection, 2 devices
Plug connector with cable connection, 3 devices
Plug connector with cable connection, 4 devices
Spare component
16A fuse for order no.: 36101, 36104, 36102, 36105, 36100
and 36103
20A fuse for order no.: 36107, 36108 and 36106
30A fuse for order no.: 36107, 36108 and 36106 for motors with
heavy starting
Electronics module device 0.075 – 0.6A for direct and reversing starters
Electronics module device 0.18 – 2.4A for direct and reversing starters
Electronics module device 1.5 – 9A for direct and reversing starters
Adapter for System 30Compact
Adapter for System 60Classic
Adapter for DIN rail mounting
20
a connection of the motor coil to a potential that i
not pa e via the MOTUS® (e.g. neutral point with
the neutral con uctor) can generate a fault me age
that require the evice to be replace for rea on of
functional afety. This fault is registered permanent-
ly in the error memory.
Pack Qty
Weight kg/100 unit
Or er no
1
34.0
36 101
1
34.0
36 104
1
34.0
36 107
1
34.7
36 102
1
34.7
36 105
1
34.7
36 108
1
34.9
36 100
1
34.9
36 103
1
34.9
36 106
1
7.6
36 902
1
8.3
36 903
1
10.0
36 904
3
0.9
31 567
3
0.9
31 568
3
0.9
31 569
1
29.2
36 109
1
29.2
36 110
1
29.2
36 111
1
4.7
36 113
1
5.5
36 114
1
5.7
36 112
3. Mounting an connecting
the main circuit
Snap the complete module including busbar or DIN rail
adapter onto the rail.
Click
Click
Click
In the case of the busbar variant, the electrical connec-
tion to the 3-phase network is established directly by
means of the adapter. When using the DIN rail adapter,
observe the terminal designations when connecting
the 3-phase network.
CAUTION: Never carry out work when voltage i
pre ent! Danger to life!
Revision 5, status 03.2016
Engli h.
The following coordination types are achieved with the
fuses used:
Coor ination type
0.6A an 2.4A variant
16A
10kA, 500V, coordination types 2
(FUSE-10X38-16A-GR)
device protection
50kA, 500V, coordination type 1
system protection
9A variant
20A
5kA, 400V, coordination types 2
(FUSE-10X38-20A-GR)
device protection
50kA, 500V, coordination type 1
system protection
30A
30kA, 500V, coordination type 1
(FUSE-ClassCC-30A-MR)
system protection
Note: 30A fu e i only nee e for motor with heavy
tarting.
Removal
To remove the busbar variants, the electronicscom-
ponent must f irst be removed from the busbar
adapter.
1.
2
1
2.
2
1
21