Wire Connection - Toshiba Carrier MMU-AP0071YHPUL Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Power supply wire
Recommended wire diameter and wire length for power supply wire.
Power supply wiring
q Electric characteristics
Model
Power Supply
MMU-AP0071YHPUL
MMU-AP0091YHPUL
208/230V-1-60 Hz
MMU-AP0121YHPUL
Control wire
Control wiring between indoor units, and outdoor unit
(2-core shielded wire)
Remote control wiring
2-core with non-polarity wire is used for wiring of the remote control wiring and group remote controls wiring.
Remote control wiring, remote control inter-unit wiring
Total wire length of remote control wiring and remote
control inter-unit wiring = L + L1 + L2 + ... Ln
Total wire length of remote control inter-unit wiring = L1 + L2 + ... Ln
Indoor unit
Indoor unit
Remote
L
control
L1
wiring
Remote controller inter-unit wiring
Remote control
NOTE
Use copper supply wire.
Use UL wire rated 600V for the power supply.
Use UL wire rated 300V for the remote control wires and control wires.
CAUTION
The remote control wire (Communication line) and AC 208/230V wires cannot be parallel to contact each other
and cannot be stored in the same conduits. If doing so, a trouble may be caused on the control system due to
noise or other factor.
27-EN
Wire size: 2 × AWG12
Up to 164'1" (50 m)
Ground
1 × AWG12 or thicker
Voltage Range (V)
MCA
Min
Max
(A)
0.18
187
253
0.19
0.20
(Up to 3280'10" (1000 m)) AWG16
Wire size
(Up to 6561'8" (2000 m)) AWG14
Wire size: AWG20
In case of wired type only
Up to 1640'5" (500 m)
In case of wireless type included
Up to 1312'4" (400 m)
Up to 656'2" (200 m)
Indoor unit
Indoor unit
L2
Ln
(Max. 8 units)

Wire connection

REQUIREMENT
Be sure to connect the wires matching the terminal numbers. Incorrect connection causes a trouble.
Be sure to pass the wires through the bushing of wiring connection port of the indoor unit.
Keep a margin (Approx. 3.9" (100 mm)) on a wire to hang down the electrical control box at servicing, etc.
The low-voltage circuit is provided for the remote controller. (Do not connect the high-voltage circuit)
MOCP
Make a loop on the wire for margin of the length so that the electrical control box can be taken out during
(A)
servicing.
15
1. Remove the screws of the terminal cover and take off.
15
2. Remove the screw of the electrical control box cover, and detach the eletrical control box cover by slide.
(The electrical control box cover is clamped onto the hinge)
15
3. Connect the power supply wire and remote controller wire to the terminal block of the electrical control box.
4. Tighten the screws of the terminal block, and fix the wires with cord clamp attached to the electrical control box.
(Do not apply tension to the connecting section of the terminal block.)
5. Mount the electrical control box cover without pinching wires.
(Mount the cover after wiring on the ceiling panel.)
Terminal cover
Hanger
* Make sure insert the terminal cover on the top of hanger.
Indoor - Outdoor
inter-unit wire /
Remote controller
wire port
– 14 –
Louver connector
Cord clamp
Electric control
(CN510:White)
box cover
Hinge
Screw
Screw
Side D (Space: 0.3" (8.5 mm))
Power supply wire port
* Cable clamp can be attached on left side.
Wire
type
Cabtyre
cable
Cabtyre
cable
Indoor - Outdoor inter-unit
wire / Remote controller
terminal block
U1 U2 A B
(L1)(L2)
Earth wire
Power supply wire
L1 L2
Power supply terminal block
Side C (Space: 0.2" (4 mm))
Cable clamping
Specification
position
3-core stranded
Side D
wire AWG14
4-core stranded
Side C
EN
wire AWG16
FR
ES
28-EN