Output Signals; [Eex Ia] Iic; Environmental Conditions; Overview Of The Parts - Camille Bauer SINEAX B 811 Mode D'emploi

Masquer les pouces Voir aussi pour SINEAX B 811:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Power supply H
AC/DC power pack (DC and 45...400 Hz)
Table 1: Nominal voltages and tolerances
Nominal voltage U
Tolerance
N
24 ... 60 V DC/AC
DC – 15 ... + 33%
AC ± 15%
85 ... 230 V
DC/AC
1
DC – 15 ... + 33%
24 ... 60 V DC/AC
AC ± 15%
85 ... 230 V AC
± 10%
85 ... 110 V DC
– 15 ... + 10%
1
For power supplies > 125 V, the auxiliary circuit should include an
external fuse.
Power input:
Communication
Bi-directional communication of digital signals with an "in-
telligent" two-wire transmitter designed for FSK and a HART
or company-specific protocol.
Frequency range:
Input circuit monitor
Pick-up level:
Signalling modes

Output signals

A1 and A12:
Frontplate signals:
Output contact AF:
Table 2: Type of output contact
Material
Symbol
Gold flashed
silver alloy
Relay approved by UL, CSA, TÜV, SEV
Instrument
version
Standard
(non-Ex)
Type of
protection
"Intrinsically
safe"

[EEx ia] IIC

Approx. 2.5 W resp. ≤ 3 VA
500 Hz ... 35 kHz
– Open-circuit
Input current < 3.6 mA,
adjustable in the works
between 1 and 4 mA
– Short-circuit
Input current > 21 mA
adjustable in the works
between 20 and 23 mA
– Linear output signal
For an open-circuit output
0 mA (with 4...20 mA)
– 5 mA (with 0...20 mA)
For a short-circuit output
approx. 26 mA
– Increasing output signal
Output approx. 115% of
full-scale value, e.g. 23 mA
for output 0/4...20 mA or
11.5 V for output 0/2...10 V
– Decreasing output signal
(only possible for live zero)
Output approx. 10% of full-
scale value, e.g. 2 mA for
output 4...20 mA or
1 V for output 2...10 V
Failure signalled by red LED
1 relais, 1 potentially-free
c h a n g e o v e r c o n t a c t ( s e e
Table 2)
Contact rating
AC: ��2 A / 250 V
(500 VA)
DC: ��1 A / 0.1...250 V
(30 W)
Direction of action:
Accuracy data (acc. to DIN/IEC 770)
Basic accuracy:

Environmental conditions

Commissioning
temperature:
Operating temperature:
Storage temperature:
Annual mean
relative humidity:
Altitude:
Vibration (IEC 68 T2/6):
Shock (IEC 68 T2/27):
Indoor use statement!

6. Overview of the parts

Figure 2 shows those parts of the device of consequence
for mounting, electrical connections and other operations
described in the Operating Instructions.
(12)
(3)
(7)
ON
(14)
(13)
Fig. 2
(3)
Front plate
(6)
Type label
(operating data)
(7)
Transparent cover
(8)
Type label (device ratings)
(9)
Fixing bracket
(10)
Opening for withdrawing
clip (for opening the
housing)
Top-hat rail 35 ×15 mm or
(11)
35×7,5 mm (EN 50 022)
Adjustable by switch
– Relay "energized" or
"de-energized" in the case
of a failure
Limit error ≤ ± 0.2%
Including linearity and reprodu-
cibility errors
– 10 to + 55 °C
– 25 to + 55 °C,
Ex – 20 to + 55 °C
– 40 to + 70 °C
≤ 75% standard climatic
rating
≤ 95% enhanced climatic
rating
2000 m max.
2 g / 5...150...5 Hz;
1 octave/min., 2 h
30 g / 11 ms
(8)
(9)
(10)
(11)
ON
(6)
(12)
Terminals
(13)
Terminals
(14)
Space for notes
ON
Green LED for signalling
operating status
Red LED for open and
short-circuit monitor
(MSK)
23

Publicité

Table des Matières
loading

Table des Matières