CUS400M Handbook
WARNING: No modification of this product is allowed.
Level of Insulation:
Dielectric Strength testing is carried out as follows:
Primary mains circuit to earth: 2.5 kVdc.
Primary mains circuits to secondary: 4.25 kVdc
Secondary circuits to earth: 2.5 kVdc.
Safety Approvals:
UL60950-1 and CSA22.2 No.60950-1 - UL Recognised. C-UL for Canada.
IEC/EN60950-1
IEC/EN/UL 62368-1 – CE mark
CE marking when applied to any CUS400M product, indicates compliance with the Low Voltage Directive
in that it complies with EN62368-1 and with the RoHS Directive.
UL/CSA 60601-1/ANSI/AAMI ES 60601-1 - UL + C -UL approval
Fusing:
Internal Dual fuses (F1 and F2) in the live and Neutral line, T8AH, 250V. (Standard CUS400M)
Internal Single fuse (F1) in the live line, T8AH, 250V. (Option /E)
Symbols:
AC
EARTH
Caution: See instructions for use
Unit Nomenclature
Note: All output voltages/variants may not be available as standard units, refer to datasheet for standard
product range. These (and other variants) may be available as non-standard or custom units, please
contact our sales team for details.
CUS400M models as described below:
Unit Product Code:
CUS400M-xxVx/yyyy
Where:
xxVx
= Channel 1 output voltage from within the output voltage adjustment range from the
Output Parameters Table below.
yyyy
= Unit options from list of standard unit options below
Blank
= open frame with potted baseplate
/B
= with metal baseplate
/C
= with M3 threaded inserts for underside mounting
/U
= with U chassis
/A
= with U chassis and cover
/F
= with U chassis and top fan
Connector options
Blank
= JST connector
M
= Molex connector
N
= Alex connector
N
L
Neutral
Live
Page 14 of 22