EN – INSTALLATION
V1550e:
Should be installed with a Ø150mm conduit, a different diameter will affect the performance
of the motor, reducing its suction capacity, increasing noise produced as well as causing
other problems.
The recommended length of the conduit between the hood and the motor is 4 m maximum,
a greater distance will reduce the motor's suction capacity, while a shorter distance will
increase the noise of the hood, if the latter case in inevitable, we recommend the use of
soundproofing elements.
It is recommended that the conduit from the hood to the motor has no sharp angles, as they
will reduce the suction capacity of the motor If they are inevitable, try to ensure they are not
too close to the inlet or outlet of the motor (at least 0.5m away). Do not use elbow joints with
an angle of less than 90º, or place one after another, the minimum recommended distance
between them is 1m, and try to make them as open as possible.
The maximum total length of the conduit from the hood to the exterior should be 10 linear
metres, not counting elbow joints (one elbow joint is equivalent to 1 linear metre), any longer
and the suction capacity of the motor will be reduced.
V2450e:
Should be installed with a Ø200mm conduit, a different diameter will affect the performance
of the motor, reducing its suction capacity, increasing noise produced as well as causing
other problems.
The recommended length of the conduit between the hood and the motor is 4 - 6 m
maximum, a greater distance will reduce the motor's suction capacity, while a shorter
distance will increase the noise of the hood, if the latter case in inevitable, we recommend
the use of soundproofing elements.
It is recommended that the conduit from the hood to the motor is without sharp angles, as
they will reduce the suction capacity of the motor. If they are inevitable, try to ensure they
are not too close to the inlet or outlet of the motor (at least 0.5m away). Do not use elbow
joints of less than 90º, or place one after another, the minimum recommended distance
between them is 1m, and try to make them as open as possible.
The maximum total length of the conduit from the hood to the exterior should be 12 linear
metres, not counting elbow joints (one elbow joint is equivalent to 2.5 linear metres), any
longer and the suction capacity of the motor will be reduced.
V3000e:
Should be installed with a Ø200mm conduit, a different diameter will affect the performance
of the motor, reducing its suction capacity, increasing noise produced as well as causing
other problems.
The recommended length of the conduit between the hood and the motor is 4 - 6 m
maximum, a greater distance will reduce the motor's suction capacity, while a shorter
distance will increase the noise of the hood, if the latter case in inevitable, we recommend
the use of soundproofing elements.
It is recommended that the conduit from the hood to the motor is without sharp angles, as
they will reduce the suction capacity of the motor. If they are inevitable, try to ensure they
are not too close to the inlet or outlet of the motor (at least 0.5m away). Do not use elbow
joints of less than 90º, or place one after another, the minimum recommended distance
between them is 1m, and try to make them as open as possible.
The maximum total length of the conduit from the hood to the exterior should be 12 linear
metres, not counting elbow joints (one elbow joint is equivalent to 2.5 linear metres), any
longer and the suction capacity of the motor will be reduced.