Maintained Switch
(1) Input 1
or
(2) Input 2
or
(3) Input 3
or
(4) Input 4
(5, 6, 7, or 8) +24VDC
LMIN-104 Terminals
3rd Party BAS
(1) Input 1
or
(2) Input 2
or
(3) Input 3
or
(4) Input 4
Dry
Contact
(5, 6, 7, or 8) +24VDC
(9) Common
LMIN-104 Terminals
POWER UP FUNCTIONALITY
LMIN-104 does not automatically bind to any loads
on initial power up. If only simple On/Off load control
is desired, loads can be assigned using standard
Push n Learn (PnL) steps.
Load Binding to Inputs:
1. Enter Push n' Learn (PnL)
Press and hold the Configuration button on the LMIN-104 (or any other DLM device in the network) for 3 seconds. The Red LED
begins to blink rapidly. Release the configuration button. The Red LED on ALL other communicating devices begins to blink rapidly.
After 1 second, load #1 turns ON. All devices that are bound to this load have their blue LED solid ON.
2. Load selection
Press and release the Configuration button to step through the loads. On the LMIN-104, press the buttons corresponding to Inputs
1-4 to bind the desired input to the load. When bound to the load, the LED for that input will light.
3. Exit Push n' Learn.
Press and hold the Configuration button for 3 seconds.

TERMINAL CONNECTIONS

2 Wire Momentary Switch
or
or
or
(5, 6, 7, or 8) +24VDC
LMIN-104 Terminals
NOTE: By default, this is a toggling input
Press once = signal sent, the Blue LED
corresponding to the input will be lit on the
LMIN-104
Press again = the relinquish command is
sent, the Blue LED corresponding to the
input will be OFF on the LMIN-104
Wattstopper Occupancy Sensor
or
System
or
Output
or
Power
Ground
LMIN-104 Terminals
See Wiring For Sensor Input
on next page
(1) Input 1
(2) Input 2
(3) Input 3
(4) Input 4
(1) Input 1
Sensor
(2) Input 2
Output
(3) Input 3
(24VDC)
(4) Input 4
Power
Ground/
(9) Common
Common
Ch 1 through Ch 4 Status:
Associated with Inputs 1-4,
LEDs track load status. They
also show bindings in PnL.
24V Overload: Indicates
24VDC current overload.
PUSH N LEARN
3
3 Wire Momentary Switch
(1) Input 1 for Switch 1
or
(3) Input 3 for Switch 2
(2) Input 2 for Switch 1
or
(4) Input 4 for Switch 2
(5, 6, 7, or 8) +24VDC
LMIN-104 Terminals
Photocell Sensor
(5, 6, 7, or 8) +24VDC
(9) Common
(10) Photocell Input
(0~10V)
LMIN-104 Terminals
See Photocell Mode
on page 7 for details

LED INDICATORS

Input 1
1
Connect to
DLM local network
Input 2
NOT Ethernet
2
Input 3
3
Input 4
4
24V Overload
Power
Ground
Sensor
Output
Blue LEDs
LED 1
LED 1
LED 2
LED 2
LED 3
LED 3
LED 4
LED 4
24V Overload