Perry Electric 1GA50917MET/P Instructions Pour L'installation Et Mode D'emploi page 16

Detecteurs de gaz naturel ou de butane/propane
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

3.i - RECORDING THE DATE OF REPLACEMENT
Note: in accordance with the reference standard, the appliance must be replaced after 5
years from installation and the replacement date indicated in the space provided on the
front of the box, as shown below (fig. 13).
!
Select the adhesive label corresponding to the month of installation (replacement) (e.g.
January = 01, October = 10), remove from the backing sheet and fix it to the appliance.
!
Select the label corresponding to the year of replacement (e.g.: Year of installation 2018 +
5 years: fix the label 2023), remove from the backing sheet and fix.
EN
!
Record the date of installation, manufacture, replacement, installation area, contractor
stamp and signature in the spaces provided alongside.
Years labels replacement
Months labels
Year of
replacement
installation
2018
01
07
2019
02
08
2020
03
09
2021
04
10
2022
05
11
2023
06
12
E.g.: with July 2018 as installation
4.i - CHECKING DETECTOR OPERATION
• Ensure that the detector has been connected to the mains for at least 1 minute.
• Spray test gas (not supplied) into the vents on the front panel of the appliance until the red LED
switches on and the buzzer sounds intermittently.
• Continue to spray the test gas, after around 30 seconds the relay is activated and closes the
solenoid valve (if connected).
• Stop spraying the gas into the detector vents and wait for a few seconds.
The appliance returns to "normal operating" status and all alarm signals are reset, the relay
is deactivated (fig. 3).
• Re-arm manually the eventual solenoid valve connected to the detector.
16
Replacement
Year of
Years
installation
2024
2023
2029
2025
2024
2030
2026
2025
2031
- - - -
2026
- - - -
sostituire entro
07
2020
mese | anno
- - - -
2027
- - - -
- - - -
2028
- - - -
07
date, attach the labels:
ENTER THE INDICATED DATA
Installation date
Manufacture date
*Replacement date
*after 5 years from date of installation
Installation area
Fig. 13
2023
Contractor stamp and signature

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

1ga50917gpl/p

Table des Matières