Install To Fit Your Application; Electrical Requirements - Honeywell TrueDRY DR65 Guide D'installation

Masquer les pouces Voir aussi pour TrueDRY DR65:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Install to Fit Your Application

Flex duct is recommended in connecting to the TrueDRY DR65 collars to reduce vibration noise.
Dedicated Return to Main Supply
A
RETURN
SEPARATE
RETURN
Main Return to Main Supply
B
RETURN
TrueDRY™ DR65 Dehumidification System 69-2089EFS—14
AIR HANDLER
SUPPLY
TrueDRY
(OPTIONAL)
GRAVITY DAMPER
BACKDRAFT
DAMPER
AIR HANDLER
SUPPLY
BACKDRAFT
DAMPER
TrueDRY
Duct Sizing: Use minimum 8-in. diameter round for duct
lengths up to 25 ft. Minimum 10-in. required for lengths
longer than 25 ft. Duct branches from the main inlet/
exhaust should be minimum 8-in. round for 2-3 branch-
es, and 8-in. round or larger for 4 branches or more.
Isolated Areas: Effective dehumidification may require
ducting to isolated or stagnant air flow areas.

Electrical requirements:

115 VAC outlet. Ground fault
interrupter (GFI) recommended.
Ideal when...
Access to a dedicated central return for
TrueDRY DR65 is available.
Combined with A/C operation; requires
backdraft damper on the exhaust port to
minimize backdraft when TrueDRY DR65
is not on but A/C is.
Providing dry air to a specific area with
M33150
an optional 20% open gravity damper on
TrueDRY DR65 supply.
Ideal when...
Running TrueDRY DR65 when not
running A/C. Requires damper on the
exhaust port to minimize backdraft when
TrueDRY DR65 is not on but A/C is.
Access to a dedicated central return for
TrueDRY DR65 is not available.
System fan should run with dehumidifier
M27324
for best results.
M24745
5

Publicité

Table des Matières
loading

Table des Matières