Function Settings - Mitsubishi Electric Mr.SLIM PKA-RP35FAL Manuel D'installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 28
6. Electrical work
ON/OFF
MODE
CHECK
TEST RUN
SET
1,4
Fig. 6-7
2
3 4
1
TEMP.
ON/OFF
F
MENU
ON/OFF
FILTER
E
BACK
MONITOR/SET
DAY
CHECK
PAR-21MAA
CLOCK
OPERATION
CLEAR
G
C
D
4
1
Fig. 6-8
1
CHECK
ON/OFF
TEMP
E
3
C,D
FAN
AUTO STOP
MODE
VANE
AUTO START
CHECK
LOUVER
h
F
A
TEST RUN
min
B
SET
RESET
CLOCK
Fig. 6-9
10
A
MODEL SELECT
TEMP
3
FAN
AUTO STOP
VANE
AUTO START
LOUVER
h
min
2
RESET
CLOCK
⁄ Mode number
1
⁄ Setting number
2
⁄ Refrigerant address
3
⁄ Unit number
4
A
TEST
B
1
2
2
CHECK
CHECK
4
CHECK
CHECK
4) Assigning a remote controller to each unit (Fig. 6-7)
Each unit can be operated only by the assigned remote controller.
Make sure each pair of an indoor unit PC board and a remote controller is assigned
to the same pair No.
5) Wireless remote controller pair number setting operation
1 Press the SET button with something sharp at the end.
Start this operation from the status of remote controller display turned off.
blinks and Model No. is lighted.
MODEL SELECT
min
2 Press the
button twice continuously.
Pair No. "0" blinks.
3 Press the temp
button to set the pair number you want to set.
4 Press the SET button with something sharp at the end.
Set pair number is lighted for three seconds then turned off.
A Pair No. of wireless remote controller
0
1
2
3–9

6.3. Function settings

6.3.1
Function setting on the unit (Selecting the unit functions)
1) For wired remote controller (Fig. 6-8)
Changing the power voltage setting
• Be sure to change the power voltage setting depending on the voltage used.
1 Go to the function setting mode.
Switch OFF the remote controller.
Press the A and B buttons simultaneously and hold them for at least 2
seconds. FUNCTION will start to flash.
2 Use the C button to set the refrigerant address (3) to 00.
3 Press D and [--] will start to flash in the unit number (4) display.
4 Use the C button to set the unit number (4) to 00.
5 Press the E MODE button to designate the refrigerant address/unit number. [--]
will flash in the mode number (1) display momentarily.
6 Press the F buttons to set the mode number (1) to 04.
7 Press the G button and the current set setting number (2) will flash.
Use the F button to switch the setting number in response to the power supply
voltage to be used.
Power supply voltage
240 V
: setting number = 1
220 V, 230 V : setting number = 2
8 Press the MODE button E and mode and the setting number (1) and (2) will
change to being on constantly and the contents of the setting can be confirmed.
9 Press the FILTER A and TEST RUN B buttons simultaneously for at least two
seconds. The function selection screen will disappear momentarily and the air
conditioner OFF display will appear.
2) For wireless remote controller (Fig. 6-9)
Changing the power voltage setting
• Be sure to change the power voltage setting depending on the voltage used.
1 Go to the function select mode
CHECK
button F twice continuously.
Press the
(Start this operation from the status of remote controller display turned off.)
is lighted and "00" blinks.
CHECK
button C once to set "50". Direct the wireless remote control-
Press the temp
ler toward the receiver of the indoor unit and press the
2 Setting the unit number
button C and D to set the unit number "00". Direct the
Press the temp
wireless remote controller toward the receiver of the indoor unit and press the
min
button B.
3 Selecting a mode
Enter 04 to change the power voltage setting using the
Direct the wireless remote controller toward the receiver of the indoor unit and
h
button A.
press the
Current setting number:
1 = 1 beep (one second)
2 = 2 beeps (one second each)
3 = 3 beeps (one second each)
4 Selecting the setting number
C and
D buttons to change the power voltage setting to 01 (240
Use the
V). Direct the wireless remote controller toward the sensor of the indoor unit and
h
button A.
press the
5 To select multiple functions continuously
Repeat steps 3 and 4 to change multiple function settings continuously.
6 Complete function selection
Direct the wireless remote controller toward the sensor of the indoor unit and
button E.
press the
Note:
Whenever changes are made to the function settings after installation or main-
tenance, be sure to record the changes with a mark in the "Setting" column of
the Function table.
6.3.2
Function setting on the remote controller
Refer to the indoor unit operation manual.
Indoor PC board
Factory setting
Cut J41
Cut J42
Cut J41, J42