Direct Electrical Connection To The Circuit Breaker, Fuse Box Or Junction Box; Cabinet Construction; Countertop Preparation - Frigidaire Gallery Série Instructions D'installation

Masquer les pouces Voir aussi pour Gallery Série:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

30" DUAL FUEL SLIDE-IN RANGE INSTALLATION INSTRUCTIONS
Direct Electrical Connection to the Circuit
Breaker, Fuse Box or Junction Box
If the appliance is connected directly to the circuit
breaker, fuse box or junction box, use flexible, armored
or nonmetallic sheathed copper cable (with grounding
wire). Supply a U.L. listed strain-relief at each end of
the cable. At the appliance end, the cable goes through
the Direct Connection Hole (see Figure 5) on the
Cord Mounting Plate. Wire sizes (copper wire only)
and connections must conform to the rating of the
appliance. A 50A time-delay fuse or circuit breaker is
recommended (minimum 40A).
Where local codes permit connecting the
appliance-grounding conductor to the neutral
(white) wire (see Figure 5):
1. Be sure that no power is supplied on the cable from
residence.
2. Remove the grounding strap from the terminal block
and from the appliance frame.
3. In the circuit breaker, fuse box or junction box:
a) Connect the green (or bare copper) wire, the
white appliance cable wire, and the neutral (white)
wire together.
b) Connect the 2 black wires together.
c) Connect the 2 red wires together.
Cable from Residence
Neutral
(white) Wire
Red
Wires
Green
(or Bare Copper)
Wire
Cable from
Appliance
NOTE: Be sure to remove the
supplied grounding strap.
Figure 5
3-Wire (Grounded Neutral) Electrical System
(Example: Junction Box)
(Models with an Electric Oven and a Gas Cooktop)
Black
Wires
Junction
Box
White Wire
U.L.-listed Conduit
Connector (or CSA
listed)
Where local codes DO NOT permit connecting
the appliance-grounding conductor to the neutral
(white) wire, or if connecting to 4-wire electrical
system (see Figure 6):
1. Be sure that no power is supplied on the cable
from residence.
2. Remove the grounding strap from the terminal
block and from the appliance frame.
3. In the circuit breaker, fuse box or junction box:
a) Connect the white appliance cable wire to the
neutral (white) wire.
b) Connect the 2 black wires together.
c) Connect the 2 red wires together.
d) Connect the green (or bare copper) grounding
wire to the grounding wire of the circuit breaker,
fuse box or junction box.
Cable from Residence
Green (or Bare
Copper) Wire
Red
Wires
Green (or Bare
Copper) Wire
Junction
Box
NOTE: Be sure to remove the
supplied grounding strap.
Figure 6 – 4-Wire Electrical System
(Example: Junction Box)
5

Cabinet Construction

To eliminate the risk of burns or fire
by reaching over heated surface units, do not have
cabinet storage space above the range. If there is
cabinet storage space above range, reduce risk by
installing a range hood that projects horizontally a
minimum of 5" (12,7 cm) beyond the bottom of the
cabinet.

Countertop Preparation

• The cooktop sides of the range fit over the cutout
edge of your countertop.
• If you have a square finish (flat) countertop, no
countertop preparation is required. Cooktop sides lay
directly on edge of countertop.
• Formed front-edged countertops must have
molded edge shaved flat 3/4" (1,9 cm) from each
front corner of opening (Figure 7).
8
White Wire
Black
Wires
White Wire
U.L.-listed Conduit
Connector (or CSA
Cable from
listed)
Appliance

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Fgds3065pf

Table des Matières