Temperature alarm

Temperature alarm – display.
The controller is equipped with a temperature alarm, that monitors the cabinet temperature.
The temperature value that activates the alarm, can be set by the user. If the temperature
exceeds the set value, the display
To reset the alarm, turn the cabinet on and off.
Setting the alarm value (setting range -35°C to +25°C – default +25°C):
P + 1
Push
+
Push
until the display shows dPL.
P
Push
to view the alarm value.
+
Use the
or
P
Push the
key to confirm the new value. Press
Setting the time delay (setting range 0 to 120 min. – default 60 min.):
Proceed as above, except the parameter for time delay is dPt.

Potential free alarm relay

Connector no. 19 on the power PCB is for connecting a remote alarm. A relay closes the circuit,
if the temperature has been too high or too low according to the set time delay.
Setting the upper alarm value (setting range -35°C to +25°C):
P + 1
Push
+
Push
until the display shows HAr.
P
Push
to view the alarm value.
+
Use the
or
P
Push the
key to confirm the new value. Press
Setting the lower alarm value (setting range -35°C to +25°C):
Proceed as above, except the parameter for lower alarm value is LAr.
Setting the time delay (setting range 0 to 120 min. – default 60 min.):
Proceed as above, except the parameters for upper and lower alarm time delay are HAt and
LAt respectively.
765041236
starts flashing according to the set time delay.
for more than 3 seconds.
-
keys to set the value.
for more than 3 seconds.
-
keys to set the value.
twice to exit the menu.