ThermoKey
Heat Exchange Solutions
TC 4. Transport and Storage
The Kit of the adiabatic system is delivered mounted for all adiabatic models.
If the equipment has to be stored before its installation (for one or more months) it is convenient to take the following
precautions:
Leave the equipment in its packing.
§
§
Store it indoors, in a room at adequate conditions: temperature (15 to 25 º C), humidity (50 to 70 %) and environment
§
§
without corrosive liquids or vapors.
The condition of the unit should be verified at the moment of reception, please check for shock marks or cracks, which could
§
§
cause damage to the equipment.
In case of damage during transportation, the transportation company should be informed immediately, in written form on
§
§
the Document of Delivery.
If the receiver accepts the goods (stamps and signs the document) without any note of non-conformity, the forwarder is not
§
§
responsible for missing packages or damaged goods.
We strongly recommend the customer to evidence damaged or missing goods on the full set of this document at the arrival
§
§
of the goods.
With a copy of it by e-mail, we can speed up corrective actions towards the forwarder and ask for insurance reimbursement.
§
§
ThermoKey should be informed regarding the damage on the equipment.
§
§
The Client should complete a written report including photographs concerning each relevant damage.
§
§
TC 5. Layout
Follow the instructions of unit installation manual and keep in consideration that not all the water sprayed will evaporate;
therefore any surplus water must be drained or recovered.
If ThermoKey doesn't provide a drain pan please make sure that the layout could change depending on customer installation.
Leave the space to connect the kit to the main pipeline.
§
§
Do not install the kit where there is wind.
§
§
Provide sufficient space between unit installed side by side to not compromise spray effect.
§
§
Provide sufficient space around the unit to permit normal operation of maintanance.
§
§
TC 5.1 NOTES
Only for adiabatic system with pump pressure: In case of equipment with low sound level (<45 dB(A) at a distance of
§
§
10 meters in free field), it will be necessary to install the pump in a technical room to guarantee the sound performance of
the equipment. If the pump is supplied separately, it is necessary to observe the diameters of the IN/OUT connections of the
drawing. For the supply of the high pressure pump ANNOVI, a flexible hose suitable for pressures of 20 bar must be used.
For any other information (e.g. working at heights) please examine the Installation and Maintenance Manual of the remote
§
§
air-cooled unit on which the adiabatic system is installed.
11
MT TC R WFS EN 03 2018
TC 6. WFS system
1
2
3
4
5
6
Detection Probe
1
Power panel + fan speed control system
2
(see control brochure)
Manometer
3
Manual valve for emergency and maintanace (M)
4
Solenoid valve to control water spray discharge
5
(MV5)
MT TC R WFS EN 03 2018
Technical Manual TC Instruction and technical data
7
8
9
Solenoid valve to control water spray charge
6
(MV4)
Finned pack with double layer fins
7
Wfs card system (see Wfs control brochure)
8
Inox tubes 22mm + Nozzles set (POM)
9
12