TC 10.4 OPERATING PROBLEMS
PROBLEM
Water is not reaching the nozzles
SOLUTION
Ensure that the inlet valve is fully opened
Ensure that the pressure and flow rate values are correct
PROBLEM
The water reaching the nozzles is not sufficient
Ensure that the inlet valve is fully opened
SOLUTION
Ensure that the pressure and flow rate values are correct
Some areas of the finned pack are not being sufficiently covered by the spray jet
PROBLEM
SOLUTION
Ensure that the pressure and flow rate values are correct
Check for the presence of foreign bodies inside the nozzles and clean them
Check if nozzles are right oriented in air direction
PROBLEM
Excessive accumulation of water inside the remote unit
SOLUTION
Check that the torque of all screws of pipe
Check for the presence of foreign bodies inside the nozzles and clean them
Ensure that the pressure and flow rate values are correct
TC 11. Spare Parts
NOZZLES (U00) - M250531
Tangential flow hollow cone+2 gaskets + Baionet collar + 2 inox screws
§
§
Materials: Plastic material (POM nozzles + Polyamid collars))
§
§
Range: 0,5 bar @ 0,20lt/min ▶ 5 bar @ 0,63lt/min
§
§
NOZZLES (U05) - M250513
Tangential flow hollow cone+2 gaskets + Baionet collar + 2 inox screws
§
§
Materials: Plastic material (POM nozzles + Polyamid collars))
§
§
Range: 0,5 bar @ 0,31lt/min ▶ 5 bar @ 1,00lt/min
§
§
INLET 1/2" MAGNETIC ELECTRO-VALVES (MV4=MV5) - M1906386
Type 1132/04S + 9 - 150/R02(HM2): 1/2" Female Gas Inlets
§
§
24V -50/60HZ-A.C.-IP65
§
§
NC = when the coil is de-energised the plunge stops the refrigerant flow
§
§
19
MT TC R WFS EN 03 2018
MAGNETIC ELECTRO-VALVES (MV4=MV5) [ONLY FOR SPECIAL DEMANDS]- M1906142
Type 1132/04A6 + 9 - 150/R02(HM2): 1/2" Female Gas Imlets
§
§
220V/230V -50/60HZ-A.C.-IP65
§
§
NC = when the coil is de-energised the plunge stops the refrigerant flow
§
§
INLET 3/4" MAGNETIC ELECTRO-VALVES (MV4) - M1906392
Type 1132/06S + 9 - 150/R02(HM2): 3/4" Female Gas Inlets
§
§
24V -50/60HZ-A.C.-IP65
§
§
NC = when the coil is de-energised the plunge stops the refrigerant flow
§
§
MAGNETIC ELECTRO-VALVES (MV5) - M1906386
Type 1132/04S + 9 - 150/R02(HM2): 1/2" Female Gas Imlets
§
§
24V -50/60HZ-A.C.-IP65
§
§
NC = when the coil is de-energised the plunge stops the refrigerant flow
§
§
MAGNETIC ELECTRO-VALVES (MV5) [ONLY FOR SPECIAL DEMANDS] - M1906142
Type 1132/04A6 + 9 - 150/R02(HM2): 1/2" Female Gas Imlets
§
§
220V/230V -50/60HZ-A.C.-IP65
§
§
NC = when the coil is de-energised the plunge stops the refrigerant flow
§
§
Nozzle
Gaskets
Collar
Manometer
MT TC R WFS EN 03 2018
Technical Manual TC Instruction and technical data
Simple assembling
Nozzle set assembled
just with a twist
on pipe
Magnetic electro-valve
20