5. Installation, reinstalling, and maintenance

Installation area
Consult with your dealer for details on installation and transferring the installation.
Caution:
Never install the air conditioner where there is a risk of leakage of flammable
gas.
If gas leaks and accumulates around the unit, fire can result.
Never install the air conditioner at the following places:
where there is a lot of machine oil
direct exposure to the ocean and beach.
where humidity is high
where there are hot springs nearby
where there is sulphuric gas
where there is a high-frequency processing machinery (a high-frequency welder,
etc.)
where acid solution is frequently used
where special sprays are frequently used
Install the indoor unit horizontally. Otherwise, water leakage can result.
Take sufficient measures against electrical noise when installing the air condi-
tioners at hospitals or communication-related businesses.
If the air conditioner is used in any of the above-mentioned environments, frequent
operational failure can be expected. It is advisable to avoid these types of installa-
tion sites. For further details, consult with the dealer.
Regarding electrical work
Caution:
The electrical work must be performed by a qualified contractor accord-
ing to the technical standard respecting electrical installation, internal
wiring rules, and the installation instruction manual with the absolute
use of exclusive circuits. The use of other products with the power source
can result in burnt-out breakers and fuses.

6. Specifications

PEFY-AF1200CFM, PEFY-AF1200CFMR
Item
Power source
Cooling capacity*1/Heating capacity*1
( ): Re-heat
Dimension
Net weight
Airflow rate
Fan
External static pressure*2
Noise level (Low-Middle-High)*2 *3
Filter
Notes: *1 Cooling/Heating capacity indicates the maximum value at operation under the following conditions:
Cooling: Indoor: 87 °F (30.5 °C) D.B./80 °F (26.7 °C) W.B.
Heating: Indoor: 32 °F (0 °C) D.B.
Pipe length: 7.5 m (24-9/16 ft)
*2 The external static pressure is set to 0.88 in. WG (220 Pa) for PEFY-AF1200CFM or 0.8 in. WG (200 Pa) for PEFY-AF1200CFMR at factory shipment.
*3 The operating sound is the data that was obtained in an anechoic room.
Model
BTU/h
kW
Height
mm [in.]
Width
mm [in.]
Depth
mm [in.]
kg [Ibs]
CFM
208V
0.4 (99.6) -0.6 (149) -0.88 (219)
0.64 (159) -0.8 (199) -1.04 (259)
230V
208V
230V
Outdoor: 87 °F (30.5 °C) D.B.
Outdoor: 32 °F (0 °C) D.B./27 °F (-2.6 °C) W.B.
Height difference: 0m (0 ft)
Never connect the grounding wire to a gas pipe, water pipe, arrester, or
telephone grounding wire. For details, consult with the dealer.
In some types of installation sites, the installation of an grand breaker is
mandatory. For details, consult with the dealer.
Regarding transfer of installation
If removing and reinstalling the air conditioner, consult with the dealer in ad-
vance to ascertain the cost of the professional engineering work.
Caution:
When moving or reinstalling the air conditioner, consult with the dealer. De-
fective installation can result in electric shock, fire, etc.
Regarding sound
In installing work, choose a place that can fully bear the weight of the air con-
ditioner, and where noise and vibration can be reduced.
Choose a place where cool or warm air and sound from the outdoor air outlet
of the air conditioner does not inconvenience the neighbors.
If any obstacles are placed near the outdoor air outlet of the air conditioner,
decreased performance and increased noise can result. Avoid placing any ob-
stacles adjacent to the air outlet.
If the air conditioner produces any abnormal sound, consult with the dealer.
Maintenance and inspection
If the air conditioner is used throughout several seasons, the internal compo-
nents can get dirty, reducing the performance.
Depending upon the conditions of usage, foul odors can be generated and
drainage can deteriorate due to dust and dirt, etc.
PEFY-AF1200CFM
208, 230V 60Hz
112,000/61,400
32.8/18.0
470 [18-9/16]
1385 [54-9/16]
1450 [57-1/8]
130 [287]
1200
41-43-46
44-46-48
Field Supplied
PEFY-AF1200CFMR
112,000/61,400 (24,200)
32.8/18.0 (7.1)
140 [309]
0.28 (70) -0.48 (120) -0.8 (200)
0.52 (130) -0.72 (180) -0.96 (240)
7

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Pefy-af1200cfmr

Table des Matières