For Wall Wash Installations, housing is to be installed
with one of (2) sides (A,B) facing the wall. (Figure 5.)
Electrical Connection
CAUTION
Make certain no bare wires are exposed outside of wire
nut connectors.
1.
Provide electrical service according to the "National
Electrical Code" or your local electrical code to the
junction box (located on the plasterframe). Supply wire
insulation must be rated for at least 90ºC. The junction
box is rated for a maximum of 8 No. 12 AWG Branch
Circuit conductors and is also suitable for at least 90ºC.
2.
Remove junction box cover. (Figure 6.)
3.
Remove appropriate round pryout and connect conduit
to junction box with proper connector (not included).
4.
Connect supply lead wires to junction box lead wires
(line, neutral and ground) in the fixture using properly
sized wire nuts. Be careful not to leave any bare
conductors outside of the wire nut connectors.
5.
Connect white to white, black to black, and green (from
electrical service) on the supply side to the bare copper
wire in the junction box. Place all excess wiring and
connections into the junction box and replace the cover.
Electrical Wiring Diagrams
1-LAMP
RED
HOT - BLACK
NEUTRAL - WHITE
Figure 7.
Installation Instructions – CD61*/CD62*/CD6S* Commercial Recessed CFL Rough-In
RED
BLUE
BLUE
BALLAST
Installation Instructions – CD61*/CD62*/CD6S* Commercial Recessed CFL Rough-In
A
Figure 5.
Figure 6.
2-LAMPS
GREEN/BARE COPPER
RED
RED
BLACK
WHITE
BALLAST
705300INS
ADP140615
www.eaton.com
B
BLACK
WHITE
YELLOW
YELLOW
LINE
NEUTRAL
GROUND
BLUE
BLUE
3