1. Safety Instructions
For skilled electricians and instructed
personnel in accordance with national
regulation, including the relevant standard and,
where applicable, in acc.with IEC 60079-17 on
electrical apparatus for explosive atmospheres.
¡The luminaires must not be operated in
Zones 0 and 20!
¡The tecnical data indicated on the
luminaires are to be observed!
¡Changes of the design and modifications to
the luminaires are not permitted!
¡The luminaires shall be operated as
intended and only in undamaged and
perfect conditions!
¡Only genuine Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
spare parts may be used for replacement!
¡Repairs that affect the explosion protection,
may only be carried out by
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A. or a qualified
Cooper Crouse-Hinds, S.A.
"electrician" and will subsequenctly have to
be cheked by an "expert"!
Do not keep these operating instructions
inside the luminaire during opertion.
¡The national safety rules and regulati-
ons for prevention of accidents and the
following safety instructions which are
marked with an (
) in theses operting
instructions, will have to be observed!
2. Conformity with standards
This explosion protected luminaires meets the
requeriment of EN50014, EN50018, EN50281-1-1
and EN60598-2-22. It also complies with the
EC Directives for"Apparatus and protective
systems for use in explosive atmospheres"
(94/9/EC) and "Electromagnetic compatibility"
(89/336/EEC).
It has been designed, manufactured and tested in
accordance to the state of the art and according to
EN29001 (ISO9001).
The luminaire are suitables for use in explosive
atmospheres,Zone 1 and 2 acc. to IEC60079-10. and
Zones 21 and 22 acc. EN50281-3.
3. Technical data
EC type examination
certificate:
LOM 03 ATEX2036X
Category of application:
II2G EExd IIC T6
II2D IP67 T85 ºC
Type:
EE 11 PL
Lamps to be use
2)
:
PL 11W
Lampholder
2GL ; EN60061-2
Approval of the production
Quality assurance:
LOM 02 ATEX 9040
Degree of protection
acc. EN60598:
IP 67
Insulation class
acc. EN60598:
I
Temperature of use:
-5
C to + 40
o
Rated voltage
230V 50/60Hz λ< 1
Electrónic:
Luminous flux ΦN/ΦE at 720/58lm
4)
Batteries
NiCd 4Ah
Autonomy
1,5h
Permanent signal
Signal status of main
connection and bateries
Telecontrol (optional)
12V DC
Material of enclosure:
Metal aloy aluminium
without Cu,painted
polyester grey.
Notes:
1) Installe in areas without mechanical risk, due the nomal operation in the industrial processe.
2) Includend in the supplying
3) On request 220V, 240V, 108-127V AC
4) 85% lm after the 1 min. and the batteries load 24h a 90% the rated voltage
Material of glass
Storage temperature in
original Packing
Terminals capacity:
Entries of cables
Direct entry:
Dimensions:
4. Installation
¡The respective national regulations as well
as the general rules of engineering which
apply to the installation and operation of
explosi-
on protected apparatus will have to be observed.
Transport and storage of the luminaire is
permitted in original packaging only!
¡Pay attention when mounting or repairing the
luminaire, dont damage the fire-finish of the glass
adquired during moulding (abrasions, sanding,
etc.) that can weaking their mechanical functions!
Opening and closing the luminaires
¡The opening of luminaire always shall be
without voltage!
¡The luminaire is well closed when the cover is
completly threaded on the luminaire enclosure!
¡See secuency in figure 2!
Not opening enclosure when explosive
atmospheres is present
Dimensions for mounting:
Accesories for mounting:
See Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A. catalogue
Cable entries
Mounting the selected cable entries
(cableglands or seals acc. needs) acc. type
and dimensions of the main conection cable,
following their manufacturer instructions.
¡The cable entries devices has to be the same
protection mode than the enclosure where they
are mounting!
Unused cabe entries have to be closed by a
correspondante certified blanking plug.
If the original blanking plugs are used , these
must be tightened with 15 Nm torque.
Main conection:
1)
Lamps mounting
¡Only must be mounting apropiated lamps for
the supplied luminaire. See indications in the
general label of the luminaire and in the present
instructions!
5.
Taking into operation
¡Prior to operation check the luminaire for
its proper funtioning and installation in
C
o
compliance with these operting instructions and
others applicable regulations!
3)
Only carry out insulation measurements between PE
and external conductor L1 (L1, L2, L3) as well as
between PE and N.
-
measurement voltage: max. 1kV AC/DC
-
min. insulation: 2 MΩ
Then the luminaire have to be tightly closed.
6.
Borosilicate
-40
C a + 60
C
o
o
2 x 2 x 2,5mm
2
PE ext.: 2 x 6mm
2
environement. Should be recycleds or eliminates
acc. the legal rules in every country.
2 x ¾" ISO 7/1,
one plugged
See figure 1.
repairing of apparatus for explosive
atmospheres, as well as the general rules of
engineering!
¡For dust explosive application, pay special
attention dont't have present clust layers abore
5mm on side of the apparatus!
Servicing
When servicing, in particular those components that
affect the explosion protection , will have to cheked,
e.g.:
See figure 1
it protection in front of the corrosion, water
ingrees and seize-up problems. Cleaning rest of
greasse and corrosion no using sharp metallic
devices who can damage the surface of the joint,
and greasing they using apropiate greasse
thermically and chemically stable with a drop
point > 200ºC like e.g.: GRASEX from
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.!
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
¡When the housing need to be repeinted, pay
attention that the flameproof joints rest without
any part with coating!
Inspection
E.g. in Spain the inspections of the installations in
See wiring diagram.
hazardous areas, have to be done by "qualified"
personnel in accordance with the Electrotechnical
Low Votage Regulation following the indications
stablished in IEC 60079-17.
to be disconnected from the main conection!
Repairing
made by "qualified" personnel!
¡The reparation of the sealed part between the
housing the glass have to be done by
Cooper Crouse-Hinds, S.A.!
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
¡ The users are not authorized to repair this
sealed part!
¡All reparations have to be done without voltage!
For repair electrical equipments in protection mode is
suggested follow the instructions indicated in
IEC 79-19.
Subject to alteration or supplement of this product
without any advertisement before.
Maintenance
This product contain a NiCd batteries than
they can be dangeureses for the
¡Observe the national rules applicable to
maintenance, servicing, inspection and
¡The responsable of the safe use of these
apparatus is the property!
Housing and glass for any cracks or damage.
The flameproof joint have to be clean,
undameged, without corrosion and perfect
greassed.
Gaskets for their perfect conditions.
Cable entries whitout corrosion.
Terminlas and blanking plugs for their firm fix.
Lamp replacement in acc. with the
manufacturer instructions.
Type of lamps used in acc. with the luminaire
specifications.
¡The flameproof of these apparatus have to
be greassed permanentlly in order to ensure
¡The nationals regulations have to be
observed!
¡When the inspections are in degree of
"Detailled" or "Closed", the luminaires have
¡The nationals regulations have to be
observed. The tasks of repairing have to be
¡Only use genuine Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
spare parts!
Cooper Crouse-Hinds, S.A.
4