About the chart:
The bar chart shows the permitted leakage fl ow rate for the airtightness classes, with the specifi ed m² and the actual
test pressure . The test value appears as a red line .
Compliant airtightness classes are shown with green bars . Non-compliant classes are shown with red bars .
10
Shows the confi gured parameter and the maximum permitted leakage fl ow
rate .
• Press the à to start the test .
• A self test is carried out before the test starts .
• The test starts once the selected pressure is reached, and continues for
fi ve minutes .
• You can interrupt the test at any time by pressing Stop .
While the test is running, the achieved pressure and the current fl ow rate
are displayed .
• After the test duration of 300 s, the device stops automatically . (Stand-
ardised test duration) If you press Stop to end the test early, the results
are displayed .
• The device indicates whether the test has passed or failed with the
specifi ed parameters .
• Press the Print key to print the report or press the New key to start a
new test .
Viewing the report before printing .
• You can use the á or â key to scroll through the report .
• Switch on the TD 600 printer and place it close to the IR window .
• Press OK to start printing .
• Note: The report is not permanently stored unless you select "Save" on
the menu .
Chart:
• Press the MENU key and press the á or â key to select Chart from the
menu .
• Confi rm by pressing the à key .
• You can print the chart by pressing the Print key on the TD 600 .
• To return to the menu press the Menu or New key once .
• To start a new test, press the Menu key twice .