"OV-DMC 3" Software
New
Establish connection with
connection
another "OV-DMC 3"
Z The camera of your
display device is activated.
f Scan the QR code on the
front side of the "OV-
DMC 3" with the camera
of your mobile device.
Z After scanning of the
code, the "OV-DMC 3"
will be connected
automatically.
Z The menu "Summary"
appears.
Cancel
Return to menu "Summary"
f Select the required connection.
Z The connection is established.
9. Select "Venting".
10. After venting has been completed, select
the required method (see Illustr. 4 on page
13).
When selecting "Measure", the
measurement starts immediately
after having pressed "Start" button.
1
2
3
4
Illustr. 5: Balanced pressure method and
computer method
106927881-V02.02.2020
(1)
Status of the connection to the "OV-
DMC 3"
(2)
Selected valve
(3)
Required parameter
(4)
Start measurement
Measurement methods
Measure
f Select "Start".
Z The measurement is carried
out.
Balanced
1. Enter the required flow rate
pressure
2. Enter the value set at the
method
regulating valve
3. Select "Start measurement"
Z A new setting for the
regulating valve is
determined during the
measurement
4. Set the determined
value and repeat the
measurement
5. Repeat the process until
the determined value
corresponds to the set
value
Commissioning
EN
14