FWECSA
GENERAL FEATURES
The FWECSA controller is designed to control all of
the system units in the Daikin range with multi-speed,
single-phase motor or coupled to an inverter for speed
modulation.
The FWECSA controller system is composed of:
•
I/O board containing the power supply circuit,
the microprocessor system and the connectors
(unscrewable) to connect the input and output devices;
•
User unit composed of graphic display and keyboard
(six keys) equipped with clock and probe to read the
room temperature.
The connection between the I/O board and the
user unit is set up using the relative connectors
and a data transmission cable fitted with a pair
of twisted conductors and shielding.
The controller makes serial communication possible on two
types of networks:
•
External Supervisor System solution: connection
to an external supervision system with MODBUS RTU
protocol on serial RS485;
•
SMALL solution: connection of multiple FWECSA
controllers in two possible configurations:
-
MASTER/SLAVE on serial RS485
-
MASTER/SLAVE on CW (Conveyed Waves),
which can also be set up with External Supervisor
System solutions.
•
Mixed net solution: connection of multiple FWECSA
controllers on different levels :
-
MASTER/SLAVE on serial RS485 (external
supervisor system or FWECSA),directions to the
slaves RS485 (called zone MASTER)
-
zone MASTER FWECSA , receiving directions from
NET MASTER RS485,transmitting directions to
SLAVES OC
-
NET SLAVES OC, working exactly to the ZONE
MASTER
FC66003946
Rev 00
Controller for units
USER MANUAL
It is strictly forbidden to reproduce this manual, even partially
MAIN FUNCTIONS
•
Automatic or manual fan speed variation (selected
from the keyboard);
•
Management of ON/OFF or modulating valves for two
or four-piped systems.
•
SUPPORTING electric heater control, used during
heating;
•
SUMMER/WINTER mode switch (= cooling/heating)
in four possible ways:
-
manually, from the keyboard;
-
manually, remotely (from digital input);
-
automatically, depending on water temperature;
-
automatically, depending on air temperature.
•
dehumidification function control;
•
operation with TIME SLOTS.
It is also supplied with:
•
External pre-consensus digital input (for example:
window contact, remote ON/OFF, presence sensor, etc.)
that can enable or disable unit operation (contact logic:
see board configuration parameters);
•
Digital switching input Remote centralised Cooling/
Heating (contact logic: see board configuration
parameters);
•
Digital input to enable ECONOMY function from
remote control (contact logic: see board configuration
parameters);
•
Water temperature probe (accessory), one or two
(optional with 4-pipe systems);
•
STANDARD room air temperature probe (installed
inside the user unit);
•
Remote room air probe (accessory) that can be used,
if connected, in place of the standard one installed in
the user interface;
•
Remote relative room air humidity probe (accessory);
•
A completely configurable digital output (dry contact).
EN