PL/X Quick Start Guide
Button abbreviations:
L
Press the Left button once
U
Press the Up button once
U/D
Press the Up button to increase the value.
Press the Down button to decrease the value.
Nx
Press the relevant button N times. This applies to all buttons. N specifies the
number of times to press the button e.g. for 5xL, press the Left button 5 times.
3.1.1
Diagnostic Summary Screens
The Diagnostic Summary Screens are displayed at power up.
SPD%
Iarm
0
0
Note:
When the display is at the top level, it toggles between the Diagnostic Summaries
approximately every 5 seconds.
Press the Left key at least 5 times (5xL) to return to these screens from any menu level.
3.1.2
Save parameters
To save the settings at any time, go first to the Diagnostic Screens (section 3.1.1), then press the
Right (R) button, Up (U) button and Right (R) button to display the Parameter Save screen. This
sequence is shown as R-U-R:
R-U-R
Press the Up (U) button to continue.
When the save is finished, press the Left button twice (2xL).
4
Installation
4.1.2
Connect the drive
Before starting to connect the drive, make sure that all power is OFF.
Make sure that power and control wiring are routed in separate conduit / cable trays and
that wiring meets all applicable national and local electrical regulations.
Make sure that the voltages on the EL1/EL2/EL3 terminals are in-phase with the voltages
on L1/L2/L3.
For reliable operation, the PL/X must control the main contactor through its CON1 and
CON2 terminals.
Drive ratings of 185kW and higher (frame sizes 3, 4 & 5) require an external power
connection for the heatsink cooling fan.
Ifld
RJSC
0
0000
R
Press the Right button once
D
Press the Down button once
SRef
Ilim
0
150
PARAMETER SAVE
UP KEY TO CONTINUE
-Ilim
Mode
-150
STOP
2
03