Special Display; Output Response; Analogue Output; Analogue Output Set To 4 - Hydac HDA 5500 Notice D'utilisation

Masquer les pouces Voir aussi pour HDA 5500:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

HDA 5500

9.2 Special display

If a measured value is set as the primary display, then by pressing the
following values can be displayed separately. These values are each displayed for approxi-
mately 3 s:
Lowest value
Peak value
Switch point(s) (depending on the model of HDA 5500)
Sensor 1, 2 or 3
The relevant lowest and peak values are reset by pressing the
ously during normal operation. If the reset has been successful, rES (reset) is displayed to
confirm this.

10 Output response

The HDA 5500 has a through analogue output, the signal of which is proportional to an input
signal. In addition, depending on the model and type, the HDA 5500 is available either
without switching outputs, or with two or four switching outputs.

10.1 Analogue output

On the analogue output a 4..20 mA or 0..10 V signal is available. The signal is proportional to
the input signal of one of the sensors or of the differential value. Both the allocation of the
output signal to sensor or differential value and the type of signal can be adjusted during
normal operation.
For setting „diFF" (Analogue output allocated to differential value (sensor 1 – sensor 2))
reference for values of sensor 2 = values of sensor 1 is an analogue output signal of 12 mA
or accordingly 5 V. From there values of sensor 2 < values of sensor 1 are shown with
signals of 0 .. 12 mA or accordingly 0 .. 5 V and values of sensor 2 > values of sensor 1 are
shown with signals of 12 .. 20 mA or accordingly 5 .. 10 V.
10.1.1 Analogue output set to 4..20 mA
Connection example for analogue output set to 4 .. 20 mA:
I
= 4 .. 20 mA
out
= 400 Ω
RL
max
Analog. Out
AGND
User Manual
or
keys the
and
keys simultane-
- 12 -

Publicité

Table des Matières
loading

Table des Matières