GB
6. Installation with sensors
The installation of the sensors varies with the type of installation (flush-
mounting or surface-mounting) and with the attachment used.
The sensor cable is factory-equipped with a connector.
Direct connection of the sensor cable to the attachment
If the attachment is equipped with a jack, the sensor is simply connected to
the attachment by plugging the connector into the jack.
The connector is polarized so that it can be plugged in only in the correct
position (see attachment operating instructions).
32
Important: The sensor cable carries safety extra low
voltage (SELV).
Observe the installation rules in acc. with VDE 0100.
GB
Flush-mounting installation of sensor cable
The sensor cable is laid in a cable duct inside the insert.
• Cut off the connector at the end of the sensor cable.
• Slide the insulating sleeve (supplied with attachments with sensor input)
over the sensor cable.
• Stick the sleeved cable through the hole (1) of the insert.
The insulating sleeve must cover the sensor cable over the full length from
the flush-mounting box to the cable duct (2).
• Pass the cable with the insulating sleeve through the duct (2) to the
terminal block (3).
The cable must follow the duct closely without any loops in the 230 V
section of the insert.
• Place the terminal block (supplied with attachments with sensor input) into
the insert as shown in the illustration (screws at the bottom).
33