Test Run; Before Test Run - Mitsubishi Electric Mr.SLIM PCA-RP HAQ Série Manuel D'installation

Masquer les pouces Voir aussi pour Mr.SLIM PCA-RP HAQ Série:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 24

7. Test run

7.1. Before test run

s After completing installation and the wiring and piping of the indoor and
outdoor units, check for refrigerant leakage, looseness in the power supply
or control wiring, wrong polarity, and no disconnection of one phase in the
supply.
s Use a 500-volt megohmmeter to check that the resistance between the power
supply terminals and ground is at least 1.0 MΩ Ω Ω Ω Ω .
F
E
D B
TEST RUN
C
COOL, HEAT
˚C
˚C
SIMPLE
TEMP.
ON/OFF
MENU
ON/OFF
FILTER
BACK
MONITOR/SET
DAY
CHECK
PAR-21MAA
CLOCK
OPERATION
CLEAR
H G
I
Fig. 7-1
B
E D
ERROR CODE
TEMP.
ON/OFF
C
MENU
ON/OFF
FILTER
BACK
MONITOR/SET
DAY
CHECK
TEST
PAR-21MAA
CLOCK
OPERATION
CLEAR
A
ERROR CODE
B
E
ERROR CODE
F
Fig. 7-2
[Output pattern A] Errors detected by indoor unit
Check code
P1
Intake sensor error
P2, P9
Pipe (Liquid or 2-phase pipe) sensor error
E6, E7
Indoor/outdoor unit communication error
P4
Drain sensor error
P5
Drain pump error
P6
Freezing/Overheating safeguard operation
EE
Communication error between indoor and outdoor units
P8
Pipe temperature error
E4
Remote controller signal receiving error
Fb
Indoor unit control system error (memory error, etc.)
– –
No corresponding
10
A ON/OFF button
B Test run display
C Indoor temperature liquid line tem-
perature display
D ON/OFF lamp
E Power display
F Error code display
Test run remaining time display
A
G Set temperature button
H Mode selection button
TEST
I Fan speed button
M TEST button
M
A CHECK button
B Refrigerant address
C TEMP. button
D IC:
Indoor unit
OC: Outdoor unit
E Check code
F Unit address
s Do not carry out this test on the control wiring (low voltage circuit) termi-
nals.
Warning:
Do not use the air conditioner if the insulation resistance is less than 1.0 MΩ Ω Ω Ω Ω .
Insulation resistance
7.2. Test run
The following 2 methods are available.
7.2.1. Using wired remote controller (Fig. 7-1)
1 Turn on the power at least 12 hours before the test run.
2 Press the [TEST] button twice. ➡ "TEST RUN" liquid crystal display
3 Press the [Mode selection] button. ➡ Make sure that wind is blown out.
4 Press the [Mode selection] button and switch to the cooling (or heating) mode.
➡ Make sure that cold (or warm) wind is blown out.
5 Press the [Fan speed] button. ➡ Make sure that the wind speed is switched.
6 Check operation of the outdoor unit fan.
7 Release test run by pressing the [ON/OFF] button. ➡ Stop
8 Register a telephone number.
The telephone number of the repair shop, sales office, etc., to contact if an error
occurs can be registered in the remote controller. The telephone number will be
displayed when an error occurs. For registration procedures, refer to the operation
manual for the indoor unit.
7.2.2. Using SW4 in outdoor unit
Refer to the outdoor unit installation manual.
7.3. Self-check (Fig. 7-2)
1 Turn on the power.
2 Press the [CHECK] button twice.
3 Set refrigerant address with [TEMP.] button if system control is used.
4 Press the [ON/OFF] button to stop the self-check.
Symptom
Remark

Publicité

Table des Matières
loading

Table des Matières