PV display: Indication of process variable
•• Indication of 'HI' or 'Lo' out of range
•• Indication of open circuit (br) or short circuit (Er)
•• Display of configuration and calibration
messages
Indication of output states:
OUT 1 (Alarm 1); OUT 2 (Alarm 2);
OUT 3 (Alarm 3)
Label with engineering units
Function key:
Gives access to different configuration stages ••
Confirms any parameter changes
• Logic input / Retransmission
output / Relay output
Isolated digital input
-
5
1500V 1500V
Ri = 5,6KΩ
(24V, 4mA)
+
6
Generic
5
user-configurable
output
6
- relay 5A/250Vac
-
Analog output for
5
retransmission
4 to 20mA, Rmax. 60Ω
+
6
• Linear input for potentiometer
4
-
3
2
Rin
>10M
+ 1,2V
(P77)
1
• Pt100 / PTC / NTC
Use wires of adequate
thickness (min. 1mm
2
)
3
PT100, JPT100,
PTC.
2
1
CPU board
S3
3 • DESCRIPTION OF FACEPLATE
4 • CONNECTIONS
External
supply
Out3
1
2
3
4
R
• Linear input with 2-wire transmitter
Ri = 50Ω
R >100Ω
20mA, Ri = 50Ω
T
T
PTC / NTC
Pt100 3-wire
Pt100 2-wire
• Device structure: identification of boards
RTD, PTC, NTC
Transmitter and
inpu
potentiometer
power supply
S3
ON
S4
OFF
S4
5
6
7
8
9
10
• Inputs
+
4...20mA
4
-
3
+
-
2
1
• Linear input (I)
dc current
linear input
4
2
(*)
1
OUTPUT board
OFF
ON
S9
S5
S8
11
"Raise" and "Lower" keys:
These keys are used for any operation that
requires a numerical parameter to be raised or
lowered. ••The speed of change is proportional to
the time the key is pressed. •• The operation is
not cyclic: once the maximum (minimum) limit is
reached, there will be no further increase
(decrease) of the value, even if the key remains
pressed.
The keys can be configured to perform reset,
hold, display of the peak value, etc. as
determined by the 't.U.' and 't.d.' parameters on
the 'In' menu.
• Outputs
Generic user-
configurable outputs
- relay 5A/250Vac
- logic 6V/20mA,
Rout = 560Ω
with power supply
>18Vac/dc
- Triac 20...240Vac
±10%, 2A max
11
12
• Power supply
Standard:
11 to 27Vac/dc ±10%
50/60Hz, 4.5VA max.
not isolated
• TC
Available thermocouples:
J, K, R, S, T, B, E, N,
L, U, G, D, C
- Respect polarities
- For extensions, use
compensated cable
appropriate for
thermocouple.
• Linear input (V)
dc voltage linear input
-
60mV, 1V, 5V, 10V,
Ri ≥ 500KΩ
(*)
+
S1
Voltage
24V (18V)
S4
S5 = Status of Out 1 relay
S8 = Status of Out 2 relay
S3
S9 = Status of Out 2 relay
A =
S7
B =
S6
TRIAC
7
~
-
Out2
Line
8
+
~
9
-
Out1
10
+
Load
!
~
11
PWR
~
12
-
2
1
+
2
-
1
+
Probe power supply
Jumpers
1V
S4 - S6B - S7A
S6B - S7A
Direct
Inverse