5b.1.1.Tailles des dispositifs de sécurité et de protection
MOTOR POWER
Up to 0,37kw at 230Vac
Up to 1,1kw at 230Vac
Up to 1,8kw at 230Vac
Up to 3kw at 230Vac
Up to 4kw at 230Vac
Up to 5,5kw at 230Vac
Up to 9,2kw at 230Vac
Up to 11kw at 230Vac
Up to 0,37kw at 400Vac
Up to 0,75kw at 400Vac
Up to 1,5kw at 400Vac
Up to 2,2kw at 400Vac
Up to 4kw at 400Vac
Up to 5,5kw at 400Vac
Up to 7,5kw at 400Vac
Up to 11kw at 400Vac
Up to 15kw at 400Vac
Up to 18,5kw at 400Vac
Up to 22kw at 400Vac
The breaking short circuit devices paired with this range must be at least 10KA, if installed in public supply networks. When
connecting to a network from a transformer substation dedicated, you must know the value declared by the supplier of the line and
use suitable equipment.
Effectuer le branchement à la terre du moteur-variateur avec résistance totale inférieure à 100 milliohm.
37/138
RECOMMENDED
RECOMMENDED
FUSE
500VAC CL.H or K5
10A
10A
15A
25A
40A
40A
50A
70A
5A
10A
10A
10A
20A
20A
30A
35A
45A
60A
70A
NEO-WiFi – manual - FRA
RECOMMENDED
INDUCTANCE
CONTACTOR
3mH
2mH
2mH
1,25mH
1,25mH
0,70mH
0,51mH
0,30mH
3mH
3mH
3mH
2mH
2mH
1,25mH
1,25mH
0,70mH
0,50mH
0,50mH
0,30mH
POWER CABLES
SECTION
mm
25A
2,5
25A
2,5
25A
2,5
45A
2,5
45A
60A
100A
100A
25A
2,5
25A
2,5
25A
2,5
25A
2,5
25A
2,5
25A
45A
45A
60A
100A
100A
REV20-LUG21
2
4
6
10
16
4
4
6
16
16
20